About Crossbar Management

Cisco MDS NX-OS Release 4.1(1b) and later supports three types of hardware for the Cisco MDS 9500
Series Directors: Generation 1, Generation 2, and Generation 3.
Generation 3 consists of hardware supported by Cisco NX-OS Release 4.1(1b) and later, including the
following:
OL-18084-01, Cisco MDS NX-OS Release 4.x
You decide to change the switch to redundant mode. Then power supply 2 is shut down.
Reason: 1800 W is the lesser of the two power supplies and it is less than the system usage.
Scenario 2: You have the following usage figures configured:
Power supply 1 = 2500 W
Additional Power supply 2 = 2200 W
Current Usage = 2000 W
Current mode = combined mode (so current capacity is 4400 W).
You decide to change the switch to redundant mode. Then the current capacity decreases to
2200 W.
Reason: 2200 W is the lesser of the two power supplies.
Scenario 3: You have the following usage figures configured:
Power supply 1 = 2500 W
Additional Power supply 2 = 1800 W
Current Usage = 3000 W
Current mode = combined mode (so current capacity is 3600 W).
You decide to change the switch to redundant mode. Then the current capacity decreases to
2500 W and the configuration is rejected.
Reason: 2500 W is less than the system usage (3000 W).
Current
Current
Mode
Usage (W)
combined
2000
N/A
2000
combined
2000
N/A
2000
combined
3000
N/A
3000
48-port 8-Gbps Fibre Channel switching module
24-port 8-Gbps Fibre Channel switching module
Power
Supply 2 (W) New Mode
1800
N/A
1800
redundant
2200
N/A
2200
redundant
1800
N/A
1800
redundant
Cisco MDS 9000 Family CLI Configuration Guide
About Crossbar Management
New
Capacity (W) Action Taken by Switch
3600
This is the existing
configuration.
2500
Power supply 2 is shut down.
4400
This is the existing
configuration.
2200
The new capacity is changed.
3600
This is the existing
configuration.
N/A
Rejected, so the mode reverts
to combined mode.