4.6.8 Set Alarm Relays

A relay configured for a Level 1 trigger will activate for both Level 1 and Level 2 alarms. A Level
2 trigger will only activate for Level 2 alarms.
None of the relays are defined as general or point specific alarms until they are programmed or
associated with one or more points in an analyzer.
Note: Set the number of fault relays before setting alarm relay definitions. If the number of fault
relays is changed, the current alarm relay definitions may change and must be redefined. See
"Configure PLC" on page  68 for more information.
Defining a point for association with a relay is a four- step process:
1. Choose the relays associate with a point.
2. Choose L1 Alarm or L2 in the Change To... area.
3. Click the square representing the point or points to associate with the relay. The point
changes color to indicate the change.
4. Choose Accept make the change the change to the configuration profile. Choosing cancel
leaves the alarm definition unchanged.
Repeat the steps for all contacts.
To verify a contacts association to analyzer points, choose the contact. The associated point
display changes color.
Note: Number of card slots vary based on PLC configuration such as number of relay cards and
relays per card.