8.8 Series 3 PLC Network Interface and Options

The Vertex M can also communicate via the local HMI, a remote HMI, via OPC tags, and via
relays as described in "Relay Output Contacts" on page  185. Additionally, the data can be
provided to a variety of fieldbuses via optional gateways. All of this is sketched in Figure 8.28.
The Vertex M presents status as an array of 244 byte as described in Table 8-10 . The values of
these data are defined in tables 8-8 and 8-9. Optional gateways translate this data into a
variety of fieldbus protocols as listed in Table 8.11. Connecting external networks directly to the
internal PLC is not supported. The Fieldbus interfaces are read-only. Write operations are either
rejected or ignored.
Protocol Name
Profibus - DP
Profinet
Modbus/TCP
Ethernet/IP
DeviceNet
ControlNet
Vertex M
Figure 8.28
Honeywell Part Number
1290-0102
1290-0105
1290-0106
1290-0107
1290-0104
1290-0103
Table 8.11
Section
See "Profibus - DP" on page 239
See "Profinet" on page 239
See "Modbus/TCP" on page 239
See "Ethernet/IP" on page 240
See "DeviceNet" on page 241
See "ControlNet" on page 243
229