Honeywell Vertex M User Manual page 196

Continuous gas monitor
Hide thumbs Also See for Vertex M:
Table of Contents

Advertisement

Tag
Folder
Count
1
1
MonStat
72
Maintenance
0
CFilter
9
Vertex M
Recommended
for most HMI
systems
Y
HMI
Y
PLC
Y
##
Az#FiltDaysLeft
196
Tag Name
Value Interpretation / Descrip-
Format
3 = Both
Reports only point-specific
faults
Unsigned integer Status
0 = No fault
1 = Maintenance Fault
2 = Instrument Fault
3 = Both
Reports only faults originating in
the HMI
Unsigned integer, Indicates the
presence of a fault for the PLC
Status
0 = No fault
1 = Maintenance Fault
2 = Instrument Fault
3 = Both
Indicates the presence of a fault
originating in the PLC.
Integer, 1 byte long, interpreted
as a bitmask. This reports status
for point as listed below:
bits 0-2 - run alarm disable
status as a 3-bit integer
0 = no data
1 = Point enabled
2 = RunTimeAlarmDisable
Relays only
3 = RunTimeAlarmDisable Full
(No gas events)
4 = RunTimePointDisable
5 = Point disabled by
configuration bits 3-4 - for HA
use only
bit 5 -- maintenance fault exists
bit 6 -- monitor fault exists
bit 7 -- for HA use only
Integer, number of days until
filters should be changed,
tion
User Manual