8.10.4 Configuration Requirements

Analog output cards should be assembled with an Ethernet IP Adaptor module that should be
connected to PLC processor module via Ethernet connection. The one end of RJ45 cable is
connected to the Link A2 of processor module. This is the rearmost connector, near to the DIN
rail and far from the LEDs. The other end connects to the Link A2 of the Ethernet IP Adapter
module as shown in the picture below. The IP address of the Ethernet IP adaptor should be
configured to 192.168.1.34. (pre-configured at factory)

8.10.5 Operational Description

The analog outputs will mirror the corresponding Fieldbus concentration register. See "Data
Values Common to Fieldbus Networks" on page  198 for more information. This section fully
describes the outputs under normal operating conditions.
Condition
Channel Output
Concentration
Normal
Value or 2 mA fault
indicator
Com
0 mA on all
Failure
channels
PLC
0 mA on all
Failure
channels
Vertex M
Notes
See "Data Values Common to Fieldbus Networks" on
page 198 2ma fault indicator must be enabled and is off
by default.
Communication link failure between PLC and Ethernet
Adaptor
Including PLC faulted or in program mode
264