Terminal Assignment of 5069-OW4I Relay Module
The 5069-OW4I digital 4-point isolated relay output module drives output devices. The data
that is sent to the module from a controller and some input modules determines the 5069-
OW4I module behavior.
Wiring:
Use minimum 18 AWG / maximum 16 AWG, 90 °C (194 °F) rated wire for load connections
l
to relay output modules.
Wire the removable terminal block (See Section Wire the Removable Terminal Block)
l
Disconnect the removable terminal block (See Section Disconnect Wires from the Removable
l
Terminal Block)
For more information about the relay output module, please refer to the Compact 5000 Digital
4-point isolated Relay Output Module Installation Instructions.
https://literature.rockwellautomation.com/idc/groups/literature/documents/in/5069-in008_-
en-p.pdf
Part # 3011-7865-001
Note: User is required to setup the relay configuration when 5069-OW4I relays are used. The
default settings do not include complete alarm and fault settings for all nine analyzers or all 72
points.
Note: The 5069-OW4I module does not use SA power. That is, it does not draw current from the
SA Power bus. The module passes it through to the next Compact 5000 I/O module in the
system.