Devicenet - Honeywell Vertex M User Manual

Continuous gas monitor
Hide thumbs Also See for Vertex M:
Table of Contents

Advertisement

8.8.7 DeviceNet

DeviceNet provides connections between simple industrial devices and higher-level devices
such as PLCs. DeviceNet network uses a combination of taps and shielded, twisted pair media
for device connection. For more information about DeviceNet, see www.odva.org. Technical
Information on the AB7833 gateway which is used in the Vertex M is available at
www.anybus.com.
The bottom of the gateway contains a bank of 8 switches which set the baud rate and MAC
address. The effect of switches 1 and 2 are listed in Table 8.14.
1
OFF
OFF
ON
ON
The effect of switches 3 to 8 are listed in Table 8.15.
MAC ID
0
1
63
As an example, the switch setting in Figure 8.44 indicates the gateway is set for 125kilobaud
and address 1.
Vertex M
Switch
2
OFF
ON
OFF
ON
Table 8.14
3
4
OFF
OFF
OFF
OFF
ON
ON
Table 8.15
Figure 8.44
Switch
5
6
OFF
OFF
OFF
OFF
ON
ON
241
Baud rate
125 k
250 k
500 k
(reserved)
7
8
OFF
OFF
OFF
ON
ON
ON