Required Tools and Equipment (ETSI)
Note
Note
Note
Note
Step 5
Verify that the ACT/STBY LED is green if this is the first powered-up TCC2/TCC2P/TCC3 card
installed, or yellow for standby if this is the second powered-up TCC2/TCC2P/TCC3. The IP address,
temperature of the node, and time of day appear on the LCD. The default time and date is 12:00 AM,
January 1, 1970.
Step 6
The LCD cycles through the IP address (the default is 192.1.0.2), node name, and software version.
Verify that the correct software version is shown on the LCD. The software text string indicates the node
type (SDH or SONET) and software release. (For example: SDH 09.20-05L-20.10 indicates it is an SDH
software load, Release 9.2. The numbers following the release number do not have any significance.)
Step 7
If the LCD shows the correct software version, continue with
correct software version, refer to your next level of technical support, upgrade the software, or remove
the TCC2/TCC2P/TCC3 card and install a replacement card.
Refer to the release-specific software upgrade document to replace the software. To replace the
TCC2/TCC2P/TCC3 card, refer to the Cisco ONS 15454 DWDM Troubleshooting Guide.
Step 8
Repeat Steps
are already installed, proceed to Step 9.
Tip
Note
Cisco ONS 15454 DWDM Procedure Guide, Release 9.2
1-78
The boot-up process is complete when the PWR LEDs turn green and the yellow ACT/STBY
remains on. (The ACT/STBY LED will be green if this is the first TCC3 card installed, and
yellow if this is the second TCC3 card installed.)
It might take up to three minutes for the A and B power alarms to clear.
Alarm LEDs might be on; disregard alarm LEDs until you are logged into CTC and can view the
Alarms tab.
If you are logged into CTC, the SFTWDOWN alarm might appear as many as two times while
the TCC3 card initializes. The alarm should clear after the card completely boots.
If the FAIL LED is on continuously, see the tip in
1
through
7
for the redundant TCC2/TCC2P/TCC3 card. If both TCC2/TCC2P/TCC3 cards
If you install a standby TCC2/TCC2P/TCC3 card that has a different software version than the
active TCC2/TCC2P/TCC3 card, the newly installed standby TCC2/TCC2P/TCC3 card
automatically copies the software version from the active TCC2/TCC2P/TCC3 card. You do not
need to do anything in this situation. However, the loading TCC2/TCC2P/TCC3 card does not
boot up in the normal manner. When the standby card is first inserted, the LEDs follow most of
the normal boot-up sequence. However, after the red FAIL LED turns on for about 5 seconds,
the FAIL LED and the ACT/STBY LED begin to flash alternately for up to 30 minutes while the
new software loads onto the active TCC2/TCC2P/TCC3 card. After loading the new software,
the upgraded TCC2/TCC2P/TCC3 card's LEDs repeat the appropriate bootup sequence, and the
amber ACT/STBY LED turns on.
If you insert a card into a slot provisioned for a different card, all LEDs turn off.
Chapter 1
Install the Cisco ONS 15454 Shelf Assembly
Step 8
about the TCC3 card automatic upload.
Step
8. If the LCD does not show the
78-19286-01