DLP-G679 Mount the ONS 15454 Shelf Assembly in a Rack (Two People)
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Note
The ONS 15454 ETSI requires 616.5 mm (24.24 inch) minimum of vertical rack space and 25 mm
(1 inch) below the installed shelf assembly to allow air flow to the fan intake. If a second
ONS 15454 ETSI is installed above a shelf assembly, the air ramp between the shelves provides space
for air flow. To ensure that the mounting is secure, use two to four M6 mounting screws for each side of
the shelf assembly. A shelf assembly should be mounted at the bottom of the rack if it is the only unit in
the rack.
Note
The ONS 15454 ANSI must have one inch (25.4 mm) of airspace below the installed shelf assembly to
allow air flow to the fan intake. If a second ONS 15454 is installed underneath a shelf assembly, the air
ramp on top of the bottom shelf assembly provides the desired space. However, if the ONS 15454 is
installed above third-party equipment, you must provide a minimum spacing of one inch (25.4 mm)
between the third-party shelf assembly and the bottom of the ONS 15454. The third-party equipment
must not vent heat upward into the ONS 15454.
Verify that the proper fuse and alarm panel has been installed in the top mounting space. If a fuse and
Step 1
alarm panel is not present, you must install one according to manufacturer's instructions:
78-19286-01
Use at least one set of the horizontal screw slots on the shelf assembly to prevent slippage.
This task allows two people to mount the shelf assembly in a rack.
Pinned hex key
# 2 Phillips Dynamometric screwdriver
ETSI only:
Two M6 x 20 socket set screws
Eight M6 x 20 pan-head Phillips mounting screws
ANSI only:
Two #12-24 x 3/4 set screws (48-1003-XX)
Eight #12-24 x 3/4 pan-head Phillips mounting screws (48-1004-XX,
48-1007-XX)
NTP-G305 Unpack and Inspect the ONS 15454 Shelf Assembly, page 1-7
As needed
Onsite
None
(ETSI only) Verify that the fuse rating does not exceed 40A.
Required Tools and Equipment (ETSI)
Cisco ONS 15454 DWDM Procedure Guide, Release 9.2
1-15