Cisco ONS 15454 Series Procedure Manual page 121

Dwdm
Hide thumbs Also See for ONS 15454 Series:
Table of Contents

Advertisement

Chapter 1
Install the Cisco ONS 15454 Shelf Assembly
NTP-G7 Install the Power and Ground
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Warning
Statement 1003
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use. Statement 39
Warning
Use copper conductors only. Statement 1025
78-19286-01
This procedure installs power feeds and grounds the ONS 15454.
ANSI and ETSI:
#2 Phillips Dynamometric screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws
Ground cable 13.3-mm² (#6 AWG) stranded
Listed pressure terminal connectors such as ring and fork types;
connectors must be suitable for #10 AWG copper conductors
Wire cutters
Wire strippers
Crimp tool
Fuse panel
ANSI only:
Power cable (from fuse and alarm panel to assembly), #10 AWG,
copper conductors, 194 degrees F [90 degrees C])
Wire wrapper
ETSI only:
Power cable (from fuse panel to MIC-A/P and to MIC-C/T/P), shipped
with the ONS 15454 ETSI
Two-hole grounding lug, shipped with the ONS 15454 ETSI
NTP-G4 Open and Remove the FMEC Cover (ETSI Only), page 1-26
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only),
page 1-31
NTP-G5 Remove the Backplane Covers (ANSI Only), page 1-29
Required
Onsite
None
Cisco ONS 15454 DWDM Procedure Guide, Release 9.2
Required Tools and Equipment (ETSI)
1-33