Cisco ONS 15454 Series Procedure Manual page 159

Dwdm
Hide thumbs Also See for ONS 15454 Series:
Table of Contents

Advertisement

Chapter 1
Install the Cisco ONS 15454 Shelf Assembly
Step 3
Align the chassis with the rack mounting screw holes; one at a time, insert and tighten the three screws.
Step 4
Connect a frame ground to the ground terminal provided on either side of the chassis. Use minimum
#14 AWG wire.
Step 5
Repeat this task as necessary for each FlexLayer shelf assembly you want to install.
Step 6
Return to your originating procedure (NTP).
DLP-G31 Install the FlexLayer Modules
Purpose
Tools/Equipment
Prerequisite Procedures None
Required/As Needed
Onsite/Remote
Security Level
Step 1
Determine the FlexLayer modules that you want to install in the FlexLayer shelf. The FlexLayer shelf
can house up to four Add/Drop FlexLayer modules or four Y-cable splitter modules.
two-channel FlexLayer modules and part numbers. Refer to the "Shelf Assembly Hardware" chapter in
the Cisco ONS 15454 DWDM Reference Manual for more information about FlexLayer modules.
Table 1-11
Part Number
15216-FLB-2-31.1=
15216-FLB-2-32.6=
15216-FLB-2-35.0=
15216-FLB-2-36.6=
15216-FLB-2-38.9=
15216-FLB-2-40.5=
15216-FLB-2-42.9=
15216-FLB-2-44.5=
15216-FLB-2-46.9=
15216-FLB-2-48.5=
15216-FLB-2-50.9=
15216-FLB-2-52.5=
15216-FLB-2-54.9=
15216-FLB-2-56.5=
78-19286-01
This task installs the FlexLayer modules in the FlexLayer shelf assembly.
You can only install two-channel FlexLayer modules.
#2 Phillips Dynamometric screwdriver
FlexLayer modules
As needed
Onsite
None
ONS 15xxx Two-Channel Add/Drop FlexLayer Module Hardware Part
Numbers
Description
ITU-100 GHz 2 Ch, FlexMod - 1530.33 and 1531.12
ITU-100 GHz 2 Ch, FlexMod - 1531.90 and 1532.68
ITU-100 GHz 2 Ch, FlexMod - 1534.25 and 1535.04
ITU-100 GHz 2 Ch, FlexMod - 1535.82 and 1536.61
ITU-100 GHz 2 Ch, FlexMod - 1538.19 and 1538.98
ITU-100 GHz 2 Ch, FlexMod - 1539.77 and 1540.56
ITU-100 GHz 2 Ch, FlexMod - 1542.14 and 1542.94
ITU-100 GHz 2 Ch, FlexMod - 1543.73 and 1544.53
ITU-100 GHz 2 Ch, FlexMod - 1546.12 and 1546.92
ITU-100 GHz 2 Ch, FlexMod - 1547.72 and 1548.51
ITU-100 GHz 2 Ch, FlexMod - 1550.12 and 1550.92
ITU-100 GHz 2 Ch, FlexMod - 1551.72 and 1552.52
ITU-100 GHz 2 Ch, FlexMod - 1554.13 and 1554.94
ITU-100 GHz 2 Ch, FlexMod - 1555.75 and 1556.55
Required Tools and Equipment (ETSI)