Install the Cisco ONS 15454 Shelf Assembly
Figure 1-5
Step 4
Repeat this task for every shelf assembly you need to install.
Step 5
Return to your originating procedure (NTP).
DLP-G8 Install the Air Ramp
Purpose
Tools/Equipment
Prerequisite Procedures None
Required/As Needed
Onsite/Remote
Security Level
The air ramp requires 50 mm of space in a standard 19-inch (482.6-mm) or 23-inch (584.2-mm) rack.
Step 1
Locate the rack mount unit (RMU) space specified in your site plan. Refer to the "Shelf Assembly
Hardware" chapter in the Cisco ONS 15454 DWDM Reference Manual for more information about air
ramp placement.
Verify the rack type of your air ramp installation. The brackets are compatible with the following racks.
Step 2
78-19286-01
Mounting the Air Ramp in a Rack
Use this task to install the air ramp for standard and deep door ONS 15454
#2 Phillips Dynamometric screwdriver
As needed
Onsite
None
19-inch racks as defined in IEC 297-1(2 Nos.)
19-inch for deep door configuration (2 Nos.)
Equipment rack
Cisco ONS 15454 DWDM Procedure Guide, Release 9.2
Required Tools and Equipment (ETSI)
1-19