Advertisement

Chapter 1
Install the Cisco ONS 15454 Shelf Assembly
DLP-G32 Install the Y-Cable Protection Modules in the FlexLayer Shelf
Purpose
Tools/Equipment
Prerequisite Procedures None
Required/As Needed
Onsite/Remote
Security Level
According to the Cisco TransportPlanner Internal Connections Report, determine the Y-cable modules
Step 1
that you want to install in the FlexLayer shelf.
Insert the appropriate Y-cable module into the FlexLayer shelf assembly. Use a Phillips Dynamometric
Step 2
screwdriver to install the two accompanying screws.
Step 3
Repeat Steps
hold up to four Y-cable modules, and the Y-cable tray can hold up to eight Y-cable modules.
Step 4
Return to your originating procedure (NTP).
DLP-G377 Install the Y-Cable Protection Modules in the Y-Cable Module Tray
Purpose
Tools/Equipment
Prerequisite Procedures None
Required/As Needed
Onsite/Remote
Security Level
Step 1
According to the Cisco TransportPlanner Internal Connections Report, determine which slots you will
use to install the Y-cable modules.
Step 2
Open the drawer of the tray by pushing inward on the latches located at the left and right front of the tray.
Step 3
In the tray, pull up the latches on either side of the module frame and slide the frame upward until it is
fully extended.
78-19286-01
This task installs the Y-cable protection modules in the FlexLayer shelf
assembly.
#2 Phillips Dynamometric screwdriver
Y-cable module(s): Multi-Mode Y-Cable Protection FlexModule(s)
(15216-CS-MM-Y) or Single-Mode Y-Cable Protection FlexModule(s)
(15216-CS-SM-Y), as appropriate
As needed
Onsite
None
1
and
2
as necessary for each Y-cable module you want to install. The FlexLayer shelf can
This task installs the Y-cable protection modules in the Y-cable module
tray. The Y-cable module tray can hold up to eight Y-cable modules.
#2 Phillips Dynamometric screwdriver
Y-cable modules: Multi-Mode Y-Cable Protection Module(s)
(15454-YCM-MM-LC) or Single-Mode Y-Cable Protection Module(s)
(15454-YCM-SM-LC), as appropriate
Cisco TransportPlanner Internal Connections Report
As needed
Onsite
None
Required Tools and Equipment (ETSI)
Cisco ONS 15454 DWDM Procedure Guide, Release 9.2
1-73