Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 6
Supervision functions
6.7.7
Table 1173:
MSCPMRI Group settings (Basic)
Parameter
Warm start level
Max Num cold start
Max Num warm start
Cnt decrease time
Table 1174:
MSCPMRI Group settings (Advanced)
Parameter
Cnt Dec timer Mult
Table 1175:
MSCPMRI Non group settings (Basic)
Parameter
Operation
6.7.8
1240
Table 1172:
MSCPMRI Output signals
Name
OPERATE
BLK_RESTART

Settings

Values (Range)
Unit
20.0...100.0
%
1...10
1...10
1...180
min
Values (Range)
Unit
1.00...10.00
Values (Range)
Unit
1=on
5=off
Monitored data
Table 1176:
MSCPMRI Monitored data
Name
COLD_COUNT
WARM_COUNT
T_RST_ENA
MSCPMRI
Type
Description
BOOLEAN
Operate signal
BOOLEAN
Restart inhibited
Step
Default
0.1
35.0
1
2
1
1
1
60
Step
Default
0.01
1.00
Step
Default
1=on
Type
Values (Range)
INT32
0...100
INT32
0...100
INT32
0...180
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS759142 C
Description
Thermal threshold to define a warm start
Maximum number of cold start allowed
Maximum number of warm start allowed
Counter decrease time
Description
Multiplier for counter decrease timer
Description
Operation Off / On
Unit
Description
Count value of cold start
Count value of warm start
min
Time left for restart when
lockstart is enabled in
minutes
Status
Technical Manual
REX640

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents