Three-Phase Current Measurement Cmmxu - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
8.1.4
8.1.4.1
8.1.4.2
8.1.4.3
REX640
Technical Manual
The deadband supervision reports a new measurement value if the input signal has
gone out of the deadband state. The deadband supervision can be used in value
reporting between the measurement point and operation control. When the deadband
supervision is properly configured, it helps to keep the communication load to a
minimum and yet measurement values are reported frequently enough.
The instantaneous measurement values of several measurement functions are
available as primary values for further use in Application Configuration. The current
values are in amperes while voltage values are in kilovolts and power values in
kilovolt-amperes, watts or volt-amperes reactive.

Three-phase current measurement CMMXU

Identification
Function description
Three-phase current measurement
Function block
GUID-63A7DBC8-7FEC-4F97-9B07-552B903BB5D9 V1 EN
Figure 703:
Function block
Functionality
The three-phase current measurement function CMMXU provides limit value
supervision output (HIGH_ALARM, HIGH_WARN, LOW_WARN, LOW_ALARM). The
delay of the activation and deactivation of these outputs can be controlled with setting
parameters On delay time and Off delay time.
Instantaneous phase currents (I_INST_A, I_INST_B and I_INST_C) are
provided as outputs in amperes. These can be used in the application configuration.
Phase current demand values (I_DMD_A, I_DMD_B and I_DMD_C) are provided as
outputs in amperes. These outputs are dedicated for Load profile recorder
(LDPRLRC).
Measurement functions
IEC 61850
IEC 60617
identification
identification
CMMXU
3I
Section 8
ANSI/IEEE C37.2
device number
IA, IB, IC
1297