Fault 17: The Reel Enable Output is Over
Current
InfoCenter Display:
Fault Description
The measured reel enable output voltage of the TEC is beyond the upper limits.
Important:
The reel engage/disengage switch is also referred to as the cutting unit enable/disable
switch and as the PTO switch.
Circuit Description
The cutting unit enable/disable switch is used to control whether the cutting reel motors are allowed to operate.
Conditions for Setting the Fault
The TEC-5002 detects that the reel enable output voltage of the TEC is beyond the upper limits.
Recommended Service Actions
Step 1: Verify that the fault repeats.
1.
Clear the system faults from the InfoCenter. Refer to
2.
Operate the machine.
Pass
The fault did not repeat. Go to
Note:
If the fault does not repeat, an isolated event has occurred.
Fail
The fault repeated. Go to Step 2.
Step 2: Test the 48 Vdc logic relay.
1.
Locate the 48 Vdc logic relay and disconnect the machine wire harness connector (P32) from the relay
(Figure
47).
_____FAULT
#17_____
Enable Out
Clearing Faults from the InfoCenter (page
Returning the Machine to Service (page 22)
70
21).
and follow the steps listed.