Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
8.1.7.5
8.1.7.6
Table 1240:
RESCMMXU Non group settings (Basic)
Parameter
Values (Range)
Operation
A Hi high limit res
A high limit res
A deadband res
REX640
Technical Manual
Table 1237:
Analog inputs
Input
IRES
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Signals

Table 1238:
RESCMMXU Input signals
Name
IRES
BLOCK
Table 1239:
RESCMMXU Output signals
Name
HIGH_ALARM
HIGH_WARN
I_INST_RES
I_DMD_RES
Settings
Unit
1=on
5=off
0.00...40.00
xIn
0.00...40.00
xIn
100...100000
Description
Residual current (measured or calculated)
Type
Default
Description
SIGNAL
-
Residual current
BOOLEAN
0=False
Block signal for all binary outputs
Type
Description
BOOLEAN
High alarm
BOOLEAN
High warning
FLOAT32
Residual current instantaneous value amplitude in
amperes
FLOAT32
Demand value of residual current
Step
Default
1=on
1
0.20
1
0.05
1
2500
Section 8
Measurement functions
Description
Operation Off / On
High alarm current limit
High warning current limit
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
1311