1MRS759142 C
8.1.10.5
8.1.10.6
Table 1261:
CSMSQI Non group settings (Basic)
Parameter
Values (Range)
Operation
Ps Seq A Hi high Lim
Ps Seq A high limit
Ps Seq A low limit
Ps Seq A low low Lim
Table continues on next page
REX640
Technical Manual
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Signals

Table 1259:
CSMSQI Input signals
Name
I3P
Table 1260:
CSMSQI Output signals
Name
I2_HIGH_AL
I2_HIGH_WARN
I1_HIGH_AL
I1_HIGH_WARN
I1_LOW_WARN
I1_LOW_AL
I0_HIGH_AL
I0_HIGH_WARN
I2_INST
I1_INST
I0_INST
Settings
Unit
1=on
5=off
0.00...40.00
xIn
0.00...40.00
xIn
0.00...40.00
xIn
0.00...40.00
xIn
Type
Default
Description
SIGNAL
-
Three-phase currents
Type
Description
BOOLEAN
Negative sequence high alarm
BOOLEAN
Negative sequence high warning
BOOLEAN
Positive sequence high alarm
BOOLEAN
Positive sequence high warning
BOOLEAN
Positive sequence low warning
BOOLEAN
Positive sequence low alarm
BOOLEAN
Zero sequence high alarm
BOOLEAN
Zero sequence high warning
FLOAT32
Negative sequence current amplitude,
instantaneous value (A)
FLOAT32
Positive sequence current amplitude,
instantaneous value (A)
FLOAT32
Zero sequence current amplitude, instantaneous
value (A)
Step
Default
1=on
1
1.40
1
1.20
1
0.00
1
0.00
Section 8
Measurement functions
Description
Operation Off / On
High alarm current limit for positive
sequence current
High warning current limit for positive
sequence current
Low warning current limit for positive
sequence current
Low alarm current limit for positive
sequence current
1319