Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 8
Measurement functions
Table 1278:
PEMMXU Non group settings (Advanced)
Parameter
Forward Wh Initial
Reverse Wh Initial
Forward VArh Initial
Reverse VArh Initial
Measurement mode
Pulse on time
Pulse off time
8.1.12.7
1330
Values (Range)
Unit
0...999999999
0...999999999
0...999999999
0...999999999
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
0.050...60.000
s
0.050...60.000
s

Monitored data

Table 1279:
PEMMXU Monitored data
Name
S-kVA:1
P-kW:1
Q-kVAr:1
PF:1
RSTACM
S_INST
S_DB
S_DMD
P_INST
P_DB
Table continues on next page
Step
Default
1
0
1
0
1
0
1
0
1=PhsA, PhsB,
PhsC
0.001
1.000
0.001
0.500
Type
Values (Range)
FLOAT32
-999999.9...9999
99.9
FLOAT32
-999999.9...9999
99.9
FLOAT32
-999999.9...9999
99.9
FLOAT32
-1.00...1.00
BOOLEAN
0=False
1=True
FLOAT32
-999999.9...9999
99.9
FLOAT32
-999999.9...9999
99.9
FLOAT32
-999999.9...9999
99.9
FLOAT32
-999999.9...9999
99.9
FLOAT32
-999999.9...9999
99.9
1MRS759142 C
Description
Preset Initial value for forward active
energy
Preset Initial value for reverse active
energy
Preset Initial value for forward reactive
energy
Preset Initial value for reverse reactive
energy
Selected measurement mode for power
calculation
Energy accumulated pulse ON time in
secs
Energy accumulated pulse OFF time in
secs
Unit
Description
kVA
Total Apparent Power
kW
Total Active Power
kVAr
Total Reactive Power
Average Power factor
Reset of accumulated
energy reading
kVA
Apparent power,
magnitude of
instantaneous value
kVA
Apparent power,
magnitude of reported
value
kVA
Demand value of
apparent power
kW
Active power, magnitude
of instantaneous value
kW
Active power, magnitude
of reported value
Technical Manual
REX640

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents