1MRS759142 C
8.1.5.5
REX640
Technical Manual
Table 1222:
Special conditions
Condition
U3P connected to real measurements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Signals

Table 1223:
VMMXU Input signals
Name
Type
U3P
SIGNAL
BLOCK
BOOLEAN
Table 1224:
VMMXU Output signals
Name
Type
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN
U_INST_AB
FLOAT32
U_INST_BC
FLOAT32
U_INST_CA
FLOAT32
U_INST_A
FLOAT32
U_INST_B
FLOAT32
U_INST_C
FLOAT32
U_DMD_AB
FLOAT32
U_DMD_BC
FLOAT32
Table continues on next page
Measurement functions
Description
The function requires that at least one voltage
channel is connected if
to "1 out of 3".
The function requires that at least two voltage
channels are connected if
set to "2 out of 3".
The function requires that all three voltage
channels are connected if
set to "3 out of 3".
Default
Description
-
Three-phase voltages
0=False
Block signal for all binary outputs
Description
High alarm
High warning
Low warning
Low alarm
Phase AB voltage instantaneous value amplitude
in kV
Phase BC voltage instantaneous value amplitude
in kV
Phase CA voltage instantaneous value amplitude
in kV
Phase A voltage instantaneous value amplitude in
kV
Phase B voltage instantaneous value amplitude in
kV
Phase C voltage instantaneous value amplitude in
kV
Demand value of U12 voltage
Demand value of U23 voltage
Section 8
Num of start phases is set
Num of start phases is
Num of start phases is
1303