4.29.4. Replacement of customer I/O power supply

Location
The customer I/O power supply is located as shown in the figure below. For the Dual Cabinet
Controller the customer I/O power supply is located in the Control Module with the same
placement.
xx0700000139
A
B
C
CAUTION!
If there are two or more Customer I/O power supply units mounted in a row and too close to
each other, there will be a heating problem and the units can be damaged.
To avoid damaging the Customer I/O power supply units, the units must be separated with 3
pcs of exterior support.
Required equipment
Equipment
Customer I/O power supply
Standard toolkit
Other tools and procedures
may be required. See
references to these
procedures in the step-by-
step instructions below.
Circuit diagram.
3HAC021313-001 Revision: P
4 Repair activities, controller IRC5
4.29.4. Replacement of customer I/O power supply
Customer I/O power supply
Power distribution board
System power supply
Spare part no.
3HAC14178-1
Art. no.
Note
DSQC 609
The contents are
defined in section
Standard toolkit.
These procedures
include references to
the tools required.
3HAC024480-004
Continues on next page