F.1.2 Implementation Table - GE N60 Instruction Manual

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

F.1 DEVICE PROFILE DOCUMENT
The following table identifies the variations, function codes, and qualifiers supported by the N60 in both request messages
and in response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or
28. For change-event objects, qualifiers 17 or 28 are always responded.
Table F–2: IMPLEMENTATION TABLE (Sheet 1 of 4)
OBJECT
OBJECT
VARIATION
DESCRIPTION
NO.
NO.
1
0
Binary Input (Variation 0 is used to request
default variation)
1
Binary Input
2
Binary Input with Status
2
0
Binary Input Change (Variation 0 is used to
request default variation)
1
Binary Input Change without Time
2
Binary Input Change with Time
3
Binary Input Change with Relative Time
10
0
Binary Output Status (Variation 0 is used to
request default variation)
F
2
Binary Output Status
12
1
Control Relay Output Block
20
0
Binary Counter
(Variation 0 is used to request default
variation)
1
32-Bit Binary Counter
Note 1:
A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. See the Communications section in Chapter 5 for
details. This optimizes the class 0 poll data size.
Note 2:
For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3:
Cold restarts are implemented the same as warm restarts – the N60 is not restarted, but the DNP process is restarted.
F-4
N60 Network Stability and Synchrophasor Measurement System
REQUEST
FUNCTION
QUALIFIER
CODES (DEC)
CODES (HEX)
1
00, 01
(read)
(start-stop)
22
06
(assign class)
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
1
00, 01
(read)
(start-stop)
22
06
(assign class)
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
1
00, 01
(read)
(start-stop)
22
06
(assign class)
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
1
06
(read)
(no range, or all)
07, 08
(limited quantity)
1
06
(read)
(no range, or all)
07, 08
(limited quantity)
1
06
(read)
(no range, or all)
07, 08
(limited quantity)
1
06
(read)
(no range, or all)
07, 08
(limited quantity)
1
00, 01
(read)
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
1
00, 01
(read)
(start-stop)
06
(no range, or all)
07, 08
(limited quantity)
17, 28
(index)
3
00, 01
(select)
(start-stop)
4
07, 08
(operate)
(limited quantity)
5
17, 28
(direct op)
(index)
6 (
dir. op, noack)
1
00, 01
(read)
(start-stop)
7
06
(freeze)
(no range, or all)
8
07, 08
(freeze noack)
(limited quantity)
9
17, 28
(freeze clear)
(index)
10
(frz. cl. noack)
22
(assign class)
1
00, 01
(read)
(start-stop)
7
06
(freeze)
(no range, or all)
8
07, 08
(freeze noack)
(limited quantity)
9
17, 28
(freeze clear)
(index)
10
(frz. cl. noack)
22
(assign class)
APPENDIX F

F.1.2 IMPLEMENTATION TABLE

RESPONSE
FUNCTION
QUALIFIER
CODES (DEC)
CODES (HEX)
129
00, 01
(response)
(start-stop)
17, 28
(index)
see Note 2)
(
129
00, 01
(response)
(start-stop)
17, 28
(index)
(see Note 2)
129
17, 28
(response)
(index)
130
(unsol. resp.)
129
17, 28
(response
(index)
130
(unsol. resp.)
129
00, 01
(response)
(start-stop)
17, 28
(index)
(see Note 2)
129
echo of request
(response)
129
00, 01
(response)
(start-stop)
17, 28
(index)
(see Note 2)