GE N60 Instruction Manual page 543

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

APPENDIX B
Value
Description
4
U2/AC8
5
U3/AC4
6
U3/AC8
7
U4/AC4
8
U4/AC8
9
U5/AC4
10
U5/AC8
11
U6/AC4
12
U6/AC8
13
U7/AC5
14
U7/AC8
15
U8/AC5
16
U8/AC8
F253
ENUMERATION: BRICK TRANSDUCER ORIGIN
Value
Description
0
None
1
U1/DC1
2
U1/DC2
3
U1/DC3
4
U2/DC1
...
...
24
U8/DC3
F256
ENUMERATION: BRICK ORIGIN/DESTINATION
Value
Description
0
None
1
U1
2
U2
3
U3
4
U4
5
U5
6
U6
7
U7
8
U8
F259
ENUMERATION: BRICK RTD TYPE
0 = 100 Ohm Nickel, 1 = 120 Ohm Nickel, 2 = 100 Ohm Platinum
F260
ENUMERATION: DATA LOGGER MODE
0 = Continuous, 1 = Trigger
F261
ENUMERATION: BANK REDUNDANCY TYPE
0 = None, 1 = Dependability Biased, 2 = Security Biased
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
F262
ENUMERATION: BRICK STATUS
0 = Disabled, 1 = OK, 2 = Communications Trouble, 3 = Equip-
ment Mismatch, 4 = Brick Trouble
F300
UR_UINT32: FLEXLOGIC BASE TYPE (15-bit type)
The FlexLogic BASE type is 7 bits and is combined with an 8-bit
descriptor and 1 bit for protection element to form a 16-bit value.
The combined bits are of the form: PTTTTTTTDDDDDDDD,
where P bit if set, indicates that the FlexLogic type is associated
with a protection element state and T represents bits for the BASE
type, and D represents bits for the descriptor.
The values in square brackets indicate the base type with P prefix
[PTTTTTTT] and the values in round brackets indicate the descrip-
tor range. The right most T bit indicates whether the type is an ON
or OFF type. There can be a total of 64 types (plus protection ele-
ments). There can be a total of 256 descriptors of each type.
[0] Off (0) – this is boolean FALSE value
[1] On (1) – this is boolean TRUE value
[2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 32)
[6] VIRTUAL OUTPUTS (1 to 64
[8] CONTACT OUTPUTS
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64)
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64)
[12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64)
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64)
[14] REMOTE INPUTS (1 to 32)
[16] DIRECT INPUTS (1 to 96)
[18] REMOTE OUTPUT DNA BIT PAIRS (1 to 32)
[20] REMOTE OUTPUT UserSt BIT PAIRS (1 to 32)
[22] REMOTE DEVICE ONLINE (1 to 16)
[24] MISCELLANEOUS EQUATION
[26] TELEPROTECTION INPUTS
[28] INSERT (via keypad only)
[30] DELETE (via keypad only)
[32] END
[34] NOT (1 INPUT)
[36] 2 INPUT XOR (0)
[38] LATCH SET/RESET (2 inputs)
[40] OR (2 to 16 inputs)
[42] AND (2 to 16 inputs)
[44] NOR (2 to 16 inputs)
[46] NAND (2 to 16 inputs)
[48] TIMER (1 to 32)
[50] ASSIGN VIRTUAL OUTPUT (1 to 64)
[52] ONE SHOT
[54] SELF-TEST ERROR (see F141 for range)
[56] PLATFORM DIRECT INPUT (1 to 96)
[58] PLATFORM DIRECT OUTPUT (1 to 96)
[60] PLATFORM DIRECT DEVICE (1 to 8)
[62] MISCELLANEOUS EVENTS (see F146 for range)
[64] PDC NETWORK CONTROL
[66] PMU RECORDER OUT OF MEMORY
[68] PMU RECORDER STOPPED
[128 to 255] ELEMENT STATES (see memory map element states
section)
B.4 MEMORY MAPPING
B-97
B

Hide quick links:

Advertisement

Table of Contents
loading