Introduction To Ac Sources - GE N60 Instruction Manual

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.1 OVERVIEW
5 SETTINGS

5.1.3 INTRODUCTION TO AC SOURCES

a) BACKGROUND
A mechanism called a source configures the routing of CT and VT input channels to measurement sub-systems. Sources,
in the context of UR series relays, refer to the logical grouping of current and voltage signals such that one source contains
all the signals required to measure the load or fault in a particular power apparatus. A given source may contain all or some
of the following signals: three-phase currents, single-phase ground current, three-phase voltages and an auxiliary voltage
from a single VT for checking for synchronism.
The basic idea of an AC source is to select a point on the power system where the voltages and currents are of interest. To
illustrate the concept of sources, as applied to current inputs only, consider the breaker-and-a-half scheme below. In this
application, the current flows as shown by the arrows. Some current flows through the upper bus bar to some other location
or power equipment, and some current flows into transformer winding 1. The current into winding 1 is the phasor sum (or
difference) of the currents in CT1 and CT2 (whether the sum or difference is used depends on the relative polarity of the CT
connections). The same considerations apply to transformer winding 2. The protection elements require access to the net
current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2.
5
Figure 5–1: BREAKER-AND-A-HALF SCHEME
In conventional analog or electronic relays, the sum of the currents is obtained from an appropriate external connection of
all CTs through which any portion of the current for the element being protected could flow. Auxiliary CTs are required to
perform ratio matching if the ratios of the primary CTs to be summed are not identical. In the UR series of relays, provisions
have been included for all the current signals to be brought to the UR device where grouping, ratio correction and summa-
tion are applied internally via configuration settings.
A major advantage of using internal summation is that the individual currents are available to the protection device; for
example, as additional information to calculate a restraint current, or to allow the provision of additional protection features
that operate on the individual currents such as breaker failure.
Given the flexibility of this approach, it becomes necessary to add configuration settings to the platform to allow the user to
select which sets of CT inputs will be added to form the net current into the protected device.
The internal grouping of current and voltage signals forms an AC source. This source can be given a specific name through
the settings, and becomes available to protection and metering elements in the UR platform. Individual names can be given
to each source to help identify them more clearly for later use. For example, in the scheme shown in the above diagram,
the user configures one source to be the sum of CT1 and CT2 and can name this source as "Wdg1 I".
Once the sources have been configured, the user has them available as selections for the choice of input signal for the pro-
tection elements and as metered quantities.
b) CT/VT MODULE CONFIGURATION
CT and VT input channels are contained in CT/VT modules. The type of input channel can be phase/neutral/other voltage,
phase/ground current, or sensitive ground current. The CT/VT modules calculate total waveform RMS levels, fundamental
frequency phasors, symmetrical components and harmonics for voltage or current, as allowed by the hardware in each
channel. These modules may calculate other parameters as directed by the CPU module.
5-6
N60 Network Stability and Synchrophasor Measurement System
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents