GE N60 Instruction Manual page 465

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 11 of 70)
ADDR
REGISTER NAME
1D8A
Frequency for Source 6
Source Demand (Read Only) (6 Modules)
1E00
Source 1 Demand Ia
1E02
Source 1 Demand Ib
1E04
Source 1 Demand Ic
1E06
Source 1 Demand Watt
1E08
Source 1 Demand Var
1E0A
Source 1 Demand Va
1E0C
Reserved (4 items)
1E10
...Repeated for Source 2
1E20
...Repeated for Source 3
1E30
...Repeated for Source 4
1E40
...Repeated for Source 5
1E50
...Repeated for Source 6
Source Demand Peaks (Read Only Non-Volatile) (6 Modules)
1E80
Source 1 Demand Ia Maximum
1E82
Source 1 Demand Ia Maximum Date
1E84
Source 1 Demand Ib Maximum
1E86
Source 1 Demand Ib Maximum Date
1E88
Source 1 Demand Ic Maximum
1E8A
Source 1 Demand Ic Maximum Date
1E8C
Source 1 Demand Watt Maximum
1E8E
Source 1 Demand Watt Maximum Date
1E90
Source 1 Demand Var
1E92
Source 1 Demand Var Maximum Date
1E94
Source 1 Demand Va Maximum
1E96
Source 1 Demand Va Maximum Date
1E98
Reserved (8 items)
1EA0
...Repeated for Source 2
1EC0
...Repeated for Source 3
1EE0
...Repeated for Source 4
1F00
...Repeated for Source 5
1F20
...Repeated for Source 6
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
Synchrocheck Actuals (Read Only) (4 Modules)
2400
Synchrocheck 1 Delta Voltage
2402
Synchrocheck 1 Delta Frequency
2403
Synchrocheck 1 Delta Phase
2404
...Repeated for Synchrocheck 2
2408
...Repeated for Synchrocheck 3
240C
...Repeated for Synchrocheck 4
Field Unit Raw Data Settings (Read/Write Setting)
2460
Field Raw Data Port
2461
Field Raw Data Freeze
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 Modules)
2540
Remote Double-point Status Input 1 Device
2541
Remote Double-point Status Input 1 Item
2542
Remote Double-point Status Input 1 Name
2548
Remote Double-point Status Input 1 Events
2549
... Repeated for double-point status input 2
2552
... Repeated for double-point status input 3
255B
... Repeated for double-point status input 4
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
2 to 90
Hz
0 to 999999.999
A
0 to 999999.999
A
0 to 999999.999
A
0 to 999999.999
W
0 to 999999.999
var
0 to 999999.999
VA
---
---
0 to 999999.999
A
0 to 4294967295
---
0 to 999999.999
A
0 to 4294967295
---
0 to 999999.999
A
0 to 4294967295
---
0 to 999999.999
W
0 to 4294967295
---
0 to 999999.999
var
0 to 4294967295
---
0 to 999999.999
VA
0 to 4294967295
---
---
---
0 to 1
---
-1000000000000 to
V
1000000000000
0 to 655.35
Hz
0 to 359.9
degrees
0 to 7
---
0 to 1
---
1 to 32
---
0 to 64
---
1 to 64
---
0 to 1
---
B.4 MEMORY MAPPING
STEP
FORMAT
DEFAULT
0.001
F003
0
0.001
F060
0
0.001
F060
0
0.001
F060
0
0.001
F060
0
0.001
F060
0
0.001
F060
0
---
F001
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
0.001
F060
0
1
F050
0
---
F001
0
1
F126
0 (No)
1
F060
0
0.01
F001
0
0.1
F001
0
1
F244
6 (H1a)
1
F102
0 (Disabled)
1
F001
1
1
F606
0 (None)
1
F205
"RemDPS Ip 1"
1
F102
0 (Disabled)
B-19
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents