APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 69 of 70)
ADDR
REGISTER NAME
EB3E
PMU 1 df/dt Trigger Dpo Time
EB3F
PMU 1 df/dt Trigger Block (3 items)
EB45
PMU 1 df/dt Trigger Target
EB46
PMU 1 df/dt Trigger Events
EB47
...Repeated for PMU 2
EB54
...Repeated for PMU 3
EB61
...Repeated for PMU 4
EB6E
...Repeated for PMU 5
EB7B
...Repeated for PMU 6
Phasor Measurement Unit Power Trigger (Read/Write Setting) (1, 2, 4, or 6 Modules)
EB88
PMU 1 Power Trigger Function
EB89
PMU 1 Power Trigger Active
EB8A
PMU 1 Power Trigger Reactive
EB8B
PMU 1 Power Trigger Apparent
EB8C
PMU 1 Power Trigger Pkp Time
EB8D
PMU 1 Power Trigger Dpo Time
EB8E
PMU 1 Power Trigger Block (3 items)
EB94
PMU 1 Power Trigger Target
EB95
PMU 1 Power Trigger Events
EB96
...Repeated for PMU 2
EBA4
...Repeated for PMU 3
EBB2
...Repeated for PMU 4
EBC0
...Repeated for PMU 5
EBCE
...Repeated for PMU 6
Phasor Measurement Unit Calibration (Read/Write Setting) (1, 2, 4, or 6 Modules)
EBDC
PMU Va Calibration Angle
EBDD
PMU Va Calibration Magnitude
EBDE
PMU Vb Calibration Angle
EBDF
PMU Vb Calibration Magnitude
EBE0
PMU Vc Calibration Angle
EBE1
PMU Vc Calibration Magnitude
EBE2
PMU Vx Calibration Angle
EBE3
PMU Vx Calibration Magnitude
EBE4
PMU Ia Calibration Angle
EBE5
PMU Ia Calibration Magnitude
EBE6
PMU Ib Calibration Angle
EBE7
PMU Ib Calibration Magnitude
EBE8
PMU Ic Calibration Angle
EBE9
PMU Ic Calibration Magnitude
EBEA
PMU Ig Calibration Angle
EBEB
PMU Ig Calibration Magnitude
EBEC
PMU Sequence Voltage Shift Angle
EBED
PMU Sequence Current Shift Angle
EBEE
...Repeated for PMU 2
EC00
...Repeated for PMU 3
EC12
...Repeated for PMU 4
EC24
...Repeated for PMU 5
EC36
...Repeated for PMU 6
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
EC48
PMU Network Reporting Function
EC49
PMU Network Reporting ID Code
EC4A
PMU TCP port number
EC4B
PMU UDP port number 1
EC4C
PMU UDP port number 2
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 600
s
0 to 4294967295
---
0 to 2
---
0 to 1
---
0 to 1
---
0.25 to 3
pu
0.25 to 3
pu
0.25 to 3
pu
0 to 600
s
0 to 600
s
0 to 4294967295
---
0 to 2
---
0 to 1
---
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-5 to 5
°
95 to 105
%
-180 to 180
°
-180 to 180
°
0 to 1
---
1 to 65534
---
1 to 65535
---
1 to 65535
---
1 to 65535
---
B.4 MEMORY MAPPING
STEP
FORMAT
DEFAULT
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
0.01
F001
1250
0.01
F001
1250
0.01
F001
1250
0.01
F001
10
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
0.05
F002
0
0.1
F002
1000
30
F002
0
30
F002
0
1
F102
0 (Disabled)
1
F001
1
1
F001
4712
1
F001
4713
1
F001
4714
B-77