6.3 METERING
The metered values for current and power demand are displayed in this menu. The "SRC 1" text will be replaced by what-
ever name was programmed by the user for the associated source (see
6
).
SOURCES
The relay measures (absolute values only) the source demand on each phase and average three phase demand for real,
reactive, and apparent power. These parameters can be monitored to reduce supplier demand penalties or for statistical
metering purposes. Demand calculations are based on the measurement type selected in the

menu. For each quantity, the relay displays the demand over the most recent demand time interval, the maxi-
DEMAND
mum demand since the last maximum demand reset, and the time and date stamp of this maximum demand value. Maxi-
mum demand quantities can be reset to zero with the
i) FREQUENCY METERING
PATH: ACTUAL VALUES
 FREQUENCY
 SRC 1
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
SOURCE FREQUENCY
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
6-20
SRC 1
DMD IC MAX:
MESSAGE
0.000
SRC 1
DMD IC DATE:
MESSAGE
2001/07/31 16:30:07
SRC 1
DMD W:
MESSAGE
0.000
SRC 1
DMD W MAX:
MESSAGE
0.000
SRC 1
DMD W DATE:
MESSAGE
2001/07/31 16:30:07
SRC 1
DMD VAR:
MESSAGE
0.000
SRC 1
DMD VAR MAX:
MESSAGE
0.000
SRC 1
DMD VAR DATE:
MESSAGE
2001/07/31 16:30:07
SRC 1
DMD VA:
MESSAGE
0.000
SRC 1
DMD VA MAX:
MESSAGE
0.000
SRC 1
DMD VA DATE:
MESSAGE
2001/07/31 16:30:07

METERING
SOURCE SRC 1
SRC 1
FREQUENCY:
0.00 Hz

settings). The signal used for frequency estimation is low-pass filtered. The
POWER SYSTEM
N60 Network Stability and Synchrophasor Measurement System
A
W
W
var
var
VA
VA
SETTINGS

CLEAR RECORDS
CLEAR DEMAND RECORDS

FREQUENCY

SETTINGS
SYSTEM SETUP
6 ACTUAL VALUES


SYSTEM SETUP
SETTINGS
PRODUCT SETUP
command.

).
SIGNAL SOURCES
SIGNAL
GE Multilin

Hide quick links: