GE N60 Instruction Manual page 497

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 43 of 70)
ADDR
REGISTER NAME
9993
Teleprotection Local Relay ID
9994
Teleprotection Terminal 1 ID
9995
Teleprotection Terminal 2 ID
9996
Reserved (10 items)
9A00
Teleprotection Input 1-n Default States (16 items)
9A10
Teleprotection Input 2-n Default States (16 items)
9A20
Teleprotection Output 1-n Operand (16 items)
9A40
Teleprotection Output 2-n Operand (16 items)
Teleprotection Channel Tests (Read Only)
9AA0
Teleprotection Channel 1 Status
9AA1
Teleprotection Channel 1 Number of Lost Packets
9AA2
Teleprotection Channel 2 Status
9AA3
Teleprotection Channel 2 Number of Lost Packets
9AA4
Teleprotection Network Status
9AAF
Teleprotection Channel 1 Input States
9AB0
Teleprotection Channel 2 Input States
9AC0
Teleprotection Input 1 States, 1 per register (16 items)
9AD0
Teleprotection Input 2 States, 1 per register (16 items)
VT Fuse Failure Settings (Read/Write) (6 Modules)
A09A
VT Fuse Failure Function
A09B
VT Fuse Failure Neutral Wire Open Function
A09C
VT Fuse Failure Neutral Wire Open 3rd Harmonic Pickup
A09D
...Repeated for module number 2
A0A0
...Repeated for module number 3
A0A3
...Repeated for module number 4
A0A6
...Repeated for module number 5
A0A9
...Repeated for module number 6
VT Fuse Failure Actual Values (Read Only) (6 Modules)
A0AC
VTFF x V0 3rd harmonic
A0AE
...Repeated for module number 2
A0B0
...Repeated for module number 3
A0B2
...Repeated for module number 4
A0B4
...Repeated for module number 5
A0B6
...Repeated for module number 6
Summator Settings (Read/Write) (6 Modules)
A0C0
Summator 1 function
A0C1
Summator 1 input mode
A0C2
Summator 1 hold
A0C4
Summator 1 pickup
A0C6
Summator 1 hysteresis
A0C7
Summator 1 input
A0CD
Summator 1 scale factor
A0D9
Summator 1 position selector
A0E5
Summator 1 units
A0E7
Summator 1 events
A0E8
Summator 1 per-unit base
A0EA
...Repeated for summator 2
A114
...Repeated for summator 3
A13E
...Repeated for summator 4
A168
...Repeated for summator 5
A192
...Repeated for summator 6
Selector Switch Actual Values (Read Only)
A210
Selector switch 1 position
A211
Selector switch 2 position
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 255
---
0 to 255
---
0 to 255
---
0 to 1
---
0 to 3
---
0 to 3
---
0 to 4294967295
---
0 to 4294967295
---
0 to 2
---
0 to 65535
---
0 to 2
---
0 to 65535
---
0 to 2
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 3
pu
0 to 999999.999
V
0 to 1
---
0 to 1
---
0 to 4294967295
---
–2000000 to 2000000
---
0.1 to 50
%
0 to 4294967295
---
–2000 to 2000
---
0 to 4294967295
---
---
---
0 to 1
---
1 to 2000000
---
1 to 7
---
1 to 7
---
B.4 MEMORY MAPPING
STEP
FORMAT
DEFAULT
1
F001
0
1
F001
0
1
F001
0
---
F001
0
1
F086
0 (Off)
1
F086
0 (Off)
1
F300
0
1
F300
0
1
F134
1 (OK)
1
F001
0
1
F134
1 (OK)
1
F001
0
1
F134
2 (n/a)
1
F500
0
1
F500
0
1
F108
0 (Off)
1
F108
0 (Off)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
0.001
F001
100
0.001
F060
0
1
F102
0 (Disabled)
1
F515
0 (Signed)
1
F300
0
0.001
F004
1000000
0.1
F001
30
1
F600
0
0.000001
F004
1000000
1
F300
0
---
F207
(none)
1
F102
0 (Disabled)
1
F004
1
1
F001
0
1
F001
1
B-51
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents