GE N60 Instruction Manual page 490

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 36 of 70)
ADDR
REGISTER NAME
Generic Comparator Settings (Read/Write Setting (6 Modules)
8010
Comparator 1 Function
8011
Comparator 1 Addition/Subtraction Mode Operand
8013
Comparator 1 Scale Factor
8014
Comparator 1 Block
B
8016
Comparator 1 Target
8017
Comparator 1 Events
8018
Comparator 1 Argument A Bits (8 items)
8028
Comparator 1 Input Mode
8029
Comparator 1 Direction Mode
802A
Comparator 1 Pickup
802C
Comparator 1 Hysteresis
802E
Comparator 1 Pickup Delay
802F
Comparator 1 Reset Delay
8030
Comparator 1 Argument B Bits (8 items)
8040
Reserved (4 items)
8044
...Repeated for Comparator 2
8078
...Repeated for Comparator 3
80AC
...Repeated for Comparator 4
80E0
...Repeated for Comparator 5
8114
...Repeated for Comparator 6
Generic Comparator Actual Values (Read Only) (6 Modules)
8150
Comparator 1 Argument A value
8152
Comparator 1 Argument B value
8154
Comparator 1 Output Value
8156
...Repeated for comparator 2
815C
...Repeated for comparator 3
8162
...Repeated for comparator 4
8168
...Repeated for comparator 5
816E
...Repeated for comparator 6
Direct Analog Input Actual Values (Read Only) (32 Modules)
8180
Direct Analog Input 1 Value
8182
Direct Analog Input 2 Value
8184
Direct Analog Input 3 Value
8186
Direct Analog Input 4 Value
8188
Direct Analog Input 5 Value
818A
Direct Analog Input 6 Value
818C
Direct Analog Input 7 Value
818E
Direct Analog Input 8 Value
8190
Direct Analog Input 9 Value
8192
Direct Analog Input 10 Value
8194
Direct Analog Input 11 Value
8196
Direct Analog Input 12 Value
8198
Direct Analog Input 13 Value
819A
Direct Analog Input 14 Value
819C
Direct Analog Input 15 Value
819E
Direct Analog Input 16 Value
81A0
Direct Analog Input 17 Value
81A2
Direct Analog Input 18 Value
81A4
Direct Analog Input 19 Value
81A6
Direct Analog Input 20 Value
81A8
Direct Analog Input 21 Value
81AA
Direct Analog Input 22 Value
81AC
Direct Analog Input 23 Value
B-44
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 1
---
0 to 4294967295
---
0.01 to 100
---
0 to 4294967295
---
0 to 2
---
0 to 1
---
0 to 4294967295
---
0 to 1
---
0 to 1
---
-25400 to 25400
---
0 to 5000
---
0 to 65.353
s
0 to 65.353
s
0 to 4294967295
---
0 to 65535
---
-12700 to 12700
---
-12700 to 12700
---
-25400 to 25400
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
0 to 2147483647
---
APPENDIX B
STEP
FORMAT
DEFAULT
1
F102
0 (Disabled)
1
F300
0
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F300
0
1
F515
0 (SIGNED)
1
F517
0 (OVER)
0.01
F004
1000000
0.01
F003
50000
0.001
F001
0
0.001
F001
0
1
F300
0
1
F001
0
0.01
F004
0
0.01
F004
0
0.01
F004
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
0.01
F060
0
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading