5 SETTINGS
The
VT NEU WIRE OPEN 1 3 HRAM PKP
WIRE OPEN detection logic to pick up.
SETTING
Function
Enabled = 1
SOURCE 1
VA
VB
VC
V_2
V_1
I_1
FLEXLOGIC OPERANDS
SRC1 50DD OP
OPEN POLE OP
The OPEN POLE OP operand applies
to the D60, L60, and L90
SETTING
Neutral Wire Open Detect
Enabled = 1
SOURCE 1
3V_0 (3rd Harmonic)
Base voltage for this element is PHASE VT SECONDARY setting in the case of WYE VTs and (PHASE VT SECONDARY)/
3
in case of DELTA VTs.
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
setting specifies the pickup level of 3rd harmonic of 3V0 signal for the VT NEU
VA’, VB’ and VC’ are the
voltage magnitude of one
cycle before
COMPARATORS
Run
|VA’|-|VA| > 0.2 pu
& |VA’| > 0.8 pu
Run
|VB’|-|VB| > 0.2 pu
OR
& |VB’| > 0.8 pu
Run
|VC’|-|VC| > 0.2 pu
& |VC’| > 0.8 pu
Run
V_2 > 0.1 pu
OR
Run
V_1 < 0.05 pu
AND
Run
I_1 > 0.075 pu
Run
TIMER
V_1 < 0.80 pu
2 cycles
Run
AND
I_1 < 0.05 pu
AND
OR
AND
AND
SETTING
3 HARM PKP
Run
AND
3V_0 3rd Harm >setting
Figure 5–84: VT FUSE FAIL SCHEME LOGIC
OR
FUSE
FAIL
TIMER
2 cycles
SET
AND
0
Latch
20 cycles
TIMER
30 cycles
RESET
0
Reset-dominant
TIMER
5 cycles
AND
0
TIMER
0
AND
20 cycles
5.7 CONTROL ELEMENTS
AND
FAULT
OR
FLEXLOGIC OPERANDS
SRC1 VT FUSE FAIL OP
SRC1 VT FUSE FAIL DPO
FLEXLOGIC OPERAND
SRC1 VT FUSE FAIL VOL LOSS
FLEXLOGIC OPERAND
OR
SRC1 VT NEU WIRE OPEN
FLEX-ANALOG
SRC1 3V0 3nd Harmonic
827093AQ.CDR
5-205