5.2 PRODUCT SETUP
When the transmit rate of the analog GOOSE communications is configured at a rate less than 1000 ms, only one
PMU can be used in the N60.
NOTE
The measured value settings for each of the 32 analog values are shown below.
PATH: SETTINGS
PRODUCT...
GGIO4 ANALOG 1(32) MEASURED VALUE
 GGIO4 ANALOG
 MEASURED VALUE
These settings are configured as follows.
5
ANALOG IN 1 VALUE: This setting selects the FlexAnalog value to drive the instantaneous value of each GGIO4 ana-
log status value (GGIO4.MX.AnIn1.instMag.f).
ANALOG IN 1 DB: This setting specifies the deadband for each analog value. Refer to IEC 61850-7-1 and 61850-7-3
for details. The deadband is used to determine when to update the deadbanded magnitude from the instantaneous
magnitude. The deadband is a percentage of the difference between the maximum and minimum values.
ANALOG IN 1 MIN: This setting specifies the minimum value for each analog value. Refer to IEC 61850-7-1 and
61850-7-3 for details. This minimum value is used to determine the deadband. The deadband is used in the determina-
tion of the deadbanded magnitude from the instantaneous magnitude.
ANALOG IN 1 MAX: This setting defines the maximum value for each analog value. Refer to IEC 61850-7-1 and
61850-7-3 for details. This maximum value is used to determine the deadband. The deadband is used in the determi-
nation of the deadbanded magnitude from the instantaneous magnitude.
Note that the
ANALOG IN 1 MIN
numbers. Because of the large range of these settings, not all values can be stored. Some values may be rounded
to the closest possible floating point number.
NOTE
The GGIO5 integer configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
 GGIO5 UINTEGER
 CONFIGURATION
5-52

COMMUNICATIONS
1
ANALOG IN
Off
ANALOG IN
MESSAGE
0.000
ANALOG IN
MESSAGE
0.000
ANALOG IN
MESSAGE
0.000
and
ANALOG IN 1 MAX

COMMUNICATIONS
GGIO5 UINT In
Off
GGIO5 UINT In
MESSAGE
Off
GGIO5 UINT In
MESSAGE
Off
GGIO5 UINT 1n 16:
MESSAGE
Off
N60 Network Stability and Synchrophasor Measurement System


IEC 61850 PROTOCOL
Range: any FlexAnalog value
1 VALUE:
Range: 0.000 to 100.000 in steps of 0.001
1 DB:
Range: –1000000000.000 to 1000000000.000 in steps
1 MIN:
Range: –1000000000.000 to 1000000000.000 in steps
1 MAX:
settings are stored as IEEE 754 / IEC 60559 floating point

IEC 61850 PROTOCOL
Range: Off, any FlexInteger
1:
Range: Off, any FlexInteger parameter
2:
Range: Off, any FlexInteger parameter
3:
Range: Off, any FlexInteger parameter
5 SETTINGS
GGIO4 ANALOG CONFIGURATION
of 0.001
of 0.001

GGIO5 ANALOG CONFIGURATION
parameter
GE Multilin