8-Bit Switches - GE N60 Instruction Manual

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.7 CONTROL ELEMENTS

PATH: SETTINGS
CONTROL ELEMENTS
 8-BIT
 SWITCH 1
5
This feature allows switching between two input arguments defined by 8 bits each. The bits are specified by FlexLogic oper-
ands. The feature could be viewed as an integrated two-position switch for 8 logic signals.
Typically this element is applied in conjunction with the Digitizer and 8-bit Comparator features.
8BIT SW 1 ARG A0 to 8BIT SW 1 ARG A7: These settings specify FlexLogic operands that constitute the first (A)
input of the switch. These operands are routed to the output operands if the control input is in the "Off" position.
BIT SW 1 ARG B0 to 8BIT SW 1 ARG B7: These settings specify FlexLogic operands that constitute the second (B)
input of the switch. These operands are routed to the output operands if the control input is in the "On" position.
8BIT SW 1 CONTROL: This setting specifies FlexLogic operands to control the routing between the A and B inputs of
the switch. If the control operand is in the "Off" state, the first (A) input is switched to the output. If the control operand
is in the "On" state, the second (B) input is switched to the output. The switching takes place instantaneously.
5-220


8-BIT SWITCHES

8BIT SWITCH 1
FUNCTION: Disabled
8BIT SW 1 ARG A0:
MESSAGE
Off
8BIT SW 1 ARG A1:
MESSAGE
Off
8BIT SW 1 ARG A7:
MESSAGE
Off
8BIT SW 1 ARG B0:
MESSAGE
Off
8BIT SW 1 ARG B1:
MESSAGE
Off
8BIT SW 1 ARG B7:
MESSAGE
Off
8BIT SW 1 CONTROL:
MESSAGE
Off
N60 Network Stability and Synchrophasor Measurement System
8-BIT SWITCH 1(6)
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand