GE N60 Instruction Manual page 460

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 6 of 70)
ADDR
REGISTER NAME
07EC
...Repeated for IEC103 Command 28
07F0
...Repeated for IEC103 Command 29
07F4
...Repeated for IEC103 Command 30
07F8
...Repeated for IEC103 Command 31
07FC
...Repeated for IEC103 Command 32
B
Digital Counter States (Read Only Non-Volatile) (8 Modules)
0800
Digital Counter 1 Value
0802
Digital Counter 1 Frozen
0804
Digital Counter 1 Frozen Time Stamp
0806
Digital Counter 1 Frozen Time Stamp us
0808
...Repeated for Digital Counter 2
0810
...Repeated for Digital Counter 3
0818
...Repeated for Digital Counter 4
0820
...Repeated for Digital Counter 5
0828
...Repeated for Digital Counter 6
0830
...Repeated for Digital Counter 7
0838
...Repeated for Digital Counter 8
FlexStates (Read Only)
0900
FlexState Bits (16 items)
Element States (Read Only)
1000
Element Operate States (64 items)
User Displays Actuals (Read Only)
1080
Formatted user-definable displays (16 items)
Modbus User Map Actuals (Read Only)
1200
User Map Values (256 items)
Direct Analog Input and Output Settings (Read/Write) (32 Modules)
1320
Direct Analog Output 1 Value
1321
Direct Analog Output 1 Deadband
1323
Direct Analog Output 1 Trigger
1325
Direct Analog Input 1 Device
1326
Direct Analog Input 1 Number
1327
Direct Analog Input 1 Units
1329
Direct Analog Input 1 Default Value
132B
Direct Analog Input 1 Mode
132C
Direct Analog Input 1 PU Base
132E
...Repeated for Direct Analog Inputs and Output 2
133C
...Repeated for Direct Analog Inputs and Output 3
134A
...Repeated for Direct Analog Inputs and Output 4
1358
...Repeated for Direct Analog Inputs and Output 5
1366
...Repeated for Direct Analog Inputs and Output 6
1374
...Repeated for Direct Analog Inputs and Output 7
1382
...Repeated for Direct Analog Inputs and Output 8
1390
...Repeated for Direct Analog Inputs and Output 9
139E
...Repeated for Direct Analog Inputs and Output 10
13AC
...Repeated for Direct Analog Inputs and Output 11
13BA
...Repeated for Direct Analog Inputs and Output 12
13C8
...Repeated for Direct Analog Inputs and Output 13
13D6
...Repeated for Direct Analog Inputs and Output 14
13E4
...Repeated for Direct Analog Inputs and Output 15
13F2
...Repeated for Direct Analog Inputs and Output 16
1400
...Repeated for Direct Analog Inputs and Output 17
140E
...Repeated for Direct Analog Inputs and Output 18
B-14
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
-2147483647 to
---
2147483647
-2147483647 to
---
2147483647
0 to 4294967295
---
0 to 4294967295
---
0 to 65535
---
0 to 65535
---
---
---
0 to 65535
---
0 to 65535
---
0 to 1000000000
---
0 to 4294967295
---
0 to 16
---
0 to 32
---
---
---
–1000000000 to
---
1000000000
0 to 1
---
1 to 2000000
---
APPENDIX B
STEP
FORMAT
DEFAULT
1
F004
0
1
F004
0
1
F050
0
1
F003
0
1
F001
0
1
F502
0
---
F200
(none)
1
F001
0
1
F600
0
0.001
F060
1000000
1
F300
0
1
F001
0
1
F001
0
---
F207
(none)
0.001
F060
1000
1
F491
0 (Default Value)
1
F003
1
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents