GE N60 Instruction Manual page 371

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5 SETTINGS
5.10 TESTING
During the PMU test mode, the physical channels (VA, VB, VC, VX, IA, IB, IC, and IG), frequency, and rate of change of fre-
quency are substituted with user values, while the symmetrical components are calculated from the physical channels. The
test values are not explicitly marked in the outgoing data frames. When required, it is recommended to use the user-pro-
grammable digital channels to signal the IEEE C37.118 client that test values are being sent in place of the real measure-
ments.
The UR Synchrophasor Implementation defines a test mode which sends a pre-defined set of Synchrophasors out over the
communication channel when the test mode function setting is enabled. In test mode, the following actions take place:
a. The Data Invalid / Test Mode bit (bit 15 in the STAT word) is set.
b. The Sim bit in all output datasets is set.
5
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
5-253

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents