GE N60 Instruction Manual page 488

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 34 of 70)
ADDR
REGISTER NAME
778E
Thermal Protection 1 Minimum Reset Time
778F
Thermal Protection 1 Reset
7791
Thermal Protection 1 Block
7793
Thermal Protection 1 Target
7794
Thermal Protection 1 Events
B
7795
Reserved (2 items)
7797
Repeated for Thermal Protection 2
Ohm Inputs (Read/Write Setting) (2 Modules)
77F8
Ohm Inputs 1 Function
77F9
Ohm Inputs 1 ID
77FF
Ohm Inputs 1 Reserved (9 items)
7808
...Repeated for Ohm Inputs 2
Phasor Measurement Unit Recorder Config Counter Command (Read/Write Command) (6 Modules)
781A
PMU 1 Recorder Clear Config Counter
781B
...Repeated for PMU 2
781C
...Repeated for PMU 3
781D
...Repeated for PMU 4
781E
...Repeated for PMU 5
781F
...Repeated for PMU 6
Phasor Measurement Unit One-shot Command (Read/Write Setting)
788C
PMU One-shot Function
788D
PMU One-shot Sequence Number
788E
PMU One-shot Time
Phasor Measurement Unit Recording Values (Read Only) (6 Modules)
7890
PMU 1 Available Records
7891
PMU 1 Second Per Record
7893
PMU 1 Last Cleared Date
7895
...Repeated for module number 2
789A
...Repeated for module number 3
78A9
...Repeated for module number 4
78A4
...Repeated for module number 5
78A9
...Repeated for module number 6
Phasor Measurement Unit Test Values (Read/Write Setting) (6 Modules)
78AE
PMU 1 Test Function
78AF
PMU 1 Phase A Voltage Test Magnitude
78B1
PMU 1 Page A Voltage Test Angle
78B2
PMU 1 Phase B Voltage Test Magnitude
78B4
PMU 1 Phase B Voltage Test Angle
78B5
PMU 1 Phase C Voltage Test Magnitude
78B7
PMU 1 Phase C Voltage Test Angle
78B8
PMU 1 Auxiliary Voltage Test Magnitude
78BA
PMU 1 Auxiliary Voltage Test Angle
78BB
PMU 1 Phase A Current Test Magnitude
78BD
PMU 1 Phase A Current Test Angle
78BE
PMU 1 Phase B Current Test Magnitude
78C0
PMU 1 Phase B Current Test Angle
78C1
PMU 1 Phase C Current Test Magnitude
78C3
PMU 1 Phase C Current Test Angle
78C4
PMU 1 Ground Current Test Magnitude
78C6
PMU 1 Ground Current Test Angle
78C7
PMU 1 Test Frequency
78C9
PMU 1 Test df/dt
78CA
...Repeated for module number 2
78E6
...Repeated for module number 3
B-42
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 1000
min.
0 to 4294967295
---
0 to 4294967295
---
0 to 2
---
0 to 1
---
---
---
0 to 1
---
---
---
0 to 65535
---
0 to 1
---
0 to 1
---
0 to 99
---
0 to 235959
---
0 to 65535
---
0 to 6553.5
---
0 to 400000000
---
0 to 1
---
0 to 700
kV
-180 to 180
°
0 to 700
kV
-180 to 180
°
0 to 700
kV
-180 to 180
°
0 to 700
kV
-180 to 180
°
0 to 9.999
kA
-180 to 180
°
0 to 9.999
kA
-180 to 180
°
0 to 9.999
kA
-180 to 180
°
0 to 9.999
kA
-180 to 180
°
20 to 70
Hz
-10 to 10
Hz/s
APPENDIX B
STEP
FORMAT
DEFAULT
1
F001
20
1
F300
0
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
---
F001
0
1
F102
0 (Disabled)
---
F205
"Ohm Ip 1 "
1
F001
0
1
F126
0 (No)
1
F102
0 (Disabled)
1
F001
1
1
F050
0
1
F001
0
0.1
F001
0
1
F050
0
1
F102
0 (Disabled)
0.01
F003
50000
0.05
F002
0
0.01
F003
50000
0.05
F002
-12000
0.01
F003
50000
0.05
F002
12000
0.01
F003
50000
0.05
F002
0
0.001
F004
1000
0.05
F002
-1000
0.001
F004
1000
0.05
F002
-13000
0.001
F003
1000
0.05
F002
11000
0.001
F004
0
0.05
F002
0
0.001
F003
60000
0.01
F002
0
GE Multilin