GE N60 Instruction Manual page 521

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 67 of 70)
ADDR
REGISTER NAME
E8CA
Aggregator 1 Protocol
E8CB
Aggregator 1 TCP Port
E8CC
Aggregator 1 UDP Port
E8CD
PMU Aggregator 1 90-5 UDP Port
E8CE
PMU Aggregator 1 PDC Network Control
E8CF
Aggregator 1 Include PMU1
E8D0
Aggregator 1 Include PMU2
E8D1
Aggregator 1 Include PMU3
E8D2
Aggregator 1 Include PMU4
E8D3
Aggregator 1 Include PMU5
E8D4
Aggregator 1 Include PMU6
E8D5
PMU Aggregator 1 ASDUS
E8D6
PMU Aggregator 1 Port
E8D7
PMU Aggregator 1 Reserved (3 items)
E8D8
...Repeated for PMU Aggregator 2
E908
...Repeated for PMU Aggregator 3
E938
...Repeated for PMU Aggregator 4
Phasor Measurement Unit Aggregator Control Block (Read/Write Setting) (1, 2, or 4 Modules)
E9C8
PMU Aggregator 1 Control Block SvEna
E9CA
PMU Aggregator 1 Control Block Client Control
E9CC
PMU Aggregator 1 CB SvEna Default
E9CE
PMU Aggregator 1 Control Block ConfRev
E9D0
PMU Aggregator 1 Control Block Priority
E9D1
PMU Aggregator 1 Control Block IPClass
E9D2
PMU Aggregator 1 Control Block VID
E9D3
PMU Aggregator 1 Control Block APPID
E9D4
PMU Aggregator 1 Control Block IP Address
E9D6
PMU Aggregator 1 Control Block Security
E9D7
...Repeated for PMU Aggregator 2
E9E6
...Repeated for PMU Aggregator 3
E9F5
...Repeated for PMU Aggregator 4
Phasor Measurement Unit Recording Command (Read/Write Command) (1, 2, 4, or 6 Modules)
EA22
PMU 1 Recording Clear Command
EA23
PMU 1 Recording Force Trigger
EA24
...Repeated for PMU 2
EA26
...Repeated for PMU 3
EA28
...Repeated for PMU 4
EA2A
...Repeated for PMU 5
EA2C
...Repeated for PMU 6
Phasor Measurement Unit Recording (Read/Write Setting)
EA2E
PMU 1 Record Function
EA2F
PMU 1 No Of Timed Records
EA30
PMU 1 Trigger Mode Ex
EA31
.PMU 1 Timed Trigger Position
Phasor Measurement Unit Recording Ex (Read/Write Setting) (6 Modules)
EA32
PMU 1 User Trigger
EA33
PMU 1 User Trigger
EA34
PMU 1 User Trigger
EA35
PMU 1 User Trigger
EA36
...Repeated for PMU 2
EA3A
...Repeated for PMU 3
EA3E
...Repeated for PMU 4
EA42
...Repeated for PMU 5
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 2
---
0 to 65534
---
0 to 65534
---
0 to 65534
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 1
---
1 to 4
---
1 to 3
---
1 to 3
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
1 to 4294967295
---
0 to 7
---
0 to 1
---
0 to 4095
---
0 to 16383
---
0 to 4294967295
---
0 to 2
---
0 to 1
---
0 to 1
---
0 to 1
---
2 to 128
---
0 to 1
---
1 to 50
%
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
B.4 MEMORY MAPPING
STEP
FORMAT
DEFAULT
1
F001
0 (NONE)
1
F001
4712
1
F001
4713
1
F001
102
1
F102
0 (Disabled)
1
F126
0 (No)
1
F126
0 (No)
1
F126
0 (No)
1
F126
0 (No)
1
F126
0 (No)
1
F126
0 (No)
1
F001
1
1
F001
1
1
F001
0
1
F300
0
1
F300
0
1
F300
0
1
F003
1
1
F001
4
1
F563
1 (Expedited
Forwarding)
1
F001
0
1
F001
0
1
F003
0
1
F001
0
1
F126
0 (No)
1
F126
0 (No)
1
F102
0 (Disabled)
1
F001
10
1
F542
0 (Auto
Overwrite)
1
F001
10
1
F300
0
1
F300
0
1
F300
0
1
F300
0
B-75
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents