GE N60 Instruction Manual page 123

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5 SETTINGS
Where the current source is the sum of two or more CTs with different nominal primary current, the primary base quantity is
the largest nominal primary current. For example, if CT1 = 300 / 5 A and CT2 = 100 / 1 A, then in order to sum these, CT2
is scaled to the CT1 ratio. In this case, the base quantity is 300 A primary, 5 A secondary for CT1, and 300/(100/1) = 3 A
secondary for CT2.
For voltage elements the primary base quantity is the nominal phase-to-phase primary voltage of the protected system pro-
vided that the VT ratio setting is set to the nominal ratio of the VTs and the secondary voltage setting is set to the phase-to-
phase voltage seen by the relay when the voltage of the protected system in nominal. The UR uses the convention that
nominal voltages in a three-phase system are phase-to-phase voltages.
For example, on a system with a 13.8 kV nominal primary voltage, the base quantity is 13800 V. With 14400:120 V delta-
connected VTs, the secondary base quantity and secondary voltage setting is:
For wye-connected VTs, the primary and secondary bases quanitities are as before, but the secondary voltage (here a
phase-to-phase ground value) is:
Many settings are common to most elements and are discussed below:
FUNCTION setting: This setting programs the element to be operational when selected as "Enabled". The factory
default is "Disabled". Once programmed to "Enabled", any element associated with the function becomes active and all
options become available.
NAME setting: This setting is used to uniquely identify the element.
SOURCE setting: This setting is used to select the AC source to be monitored. See the Introduction to AC Sources
section later.
PICKUP setting: For simple elements, this setting is used to program the level of the measured parameter above or
below which the pickup state is established. In more complex elements, a set of settings may be provided to define the
range of the measured parameters which will cause the element to pickup.
PICKUP DELAY setting: This setting sets a time-delay-on-pickup, or on-delay, for the duration between the pickup
and operate output states.
RESET DELAY setting: This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the
Operate output state and the return to logic 0 after the input transits outside the defined pickup range.
BLOCK setting: The default output operand state of all comparators is a logic 0 or "flag not set". The comparator
remains in this default state until a logic 1 is asserted at the RUN input, allowing the test to be performed. If the RUN
input changes to logic 0 at any time, the comparator returns to the default state. The RUN input is used to supervise
the comparator. The BLOCK input is used as one of the inputs to RUN control.
TARGET setting: This setting is used to define the operation of an element target message. When set to "Disabled",
no target message or illumination of a faceplate LED indicator is issued upon operation of the element. When set to
"Self-Reset", the target message and LED indication follow the operate state of the element, and self-resets once the
operate element condition clears. When set to "Latched", the target message and LED indication will remain visible
after the element output returns to logic 0 until a RESET command is received by the relay.
EVENTS setting: This setting is used to control whether the pickup, dropout or operate states are recorded by the
event recorder. When set to "Disabled", element pickup, dropout or operate are not recorded as events. When set to
"Enabled", events are created for:
(Element) PKP (pickup)
(Element) DPO (dropout)
(Element) OP (operate)
The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to
the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not 0.
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
13800
--------------- -
120
115 V
=
14400
13800
120
--------------- -
--------- -
66.4 V
=
14400
3
5.1 OVERVIEW
(EQ 5.1)
(EQ 5.2)
5
5-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents