5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
ADDRESSES
 IEC NETWORK
 CLIENT ADDRESSES
The N60 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the N60 can connect.
A maximum of two simultaneous connections are supported at any given time.
5
p) IEC 60870-5-103 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC103
 PROTOCOL
The N60 is provided with optional IEC 60870-5-103 communications capability. This feature is specified as
a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
The IEC 60870-5-103 protocol is enabled when the
ting is set to IEC 60870-5-103.
IEC103 COMMON ADDRESS OF ASDU
254. This ID does not need to be in sequential order for all stations that communicate with a controller, but it is recom-
mended. Note that RS485 only allows a maximum of 32 slave stations on a communication line, so the entire range of 254
addresses is never exhausted.
: This setting defines the time that the N60 waits for a synchronization message. The N60 synchro-
IEC103 SYNC TIMEOUT
nizes its clock using all available sources, with the source synching more frequently overwriting the time of the other
sources. Since the synchronization message received from the IEC 60870-5-103 master is less frequent than IRIG-B, PTP,
or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs and
none of IRIG-B, PTP, or SNTP is active, the N60 sets the invalid bit in the time stamp of a time-tagged message.
5-58

COMMUNICATIONS
CLIENT ADDRESS 1:
0.0.0.0
CLIENT ADDRESS 2:
MESSAGE
0.0.0.0
CLIENT ADDRESS 3:
MESSAGE
0.0.0.0
CLIENT ADDRESS 4:
MESSAGE
0.0.0.0
CLIENT ADDRESS 5:
MESSAGE
0.0.0.0

COMMUNICATIONS
IEC103 COMMON
ADDRESS OF ASDU: 0
IEC103 SYNC TIMEOUT:
MESSAGE
1
 IEC103 INPUTS
MESSAGE
 BINARY
 IEC103 INPUTS
MESSAGE
 MEASURANDS
 IEC103 COMMANDS
MESSAGE
: This setting uniquely defines this N60 on the serial line. Select an ID between 0 and
N60 Network Stability and Synchrophasor Measurement System

IEC 60870-5-104 PROTOCOL
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format

IEC 60870-5-103
Range: 0 to 254 in steps of 1
Range: 1 to 1440 min in steps of 1
Range: see sub-menu below
Range: see sub-menu below
Range: see sub-menu below