GE N60 Instruction Manual page 384

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

6.2 STATUS
PATH: ACTUAL VALUES
 PRP
The N60 Network Stability and Synchrophasor Measurement System is provided with optional PRP capa-
bility. This feature is specified as a software option at the time of ordering. See the Order Codes section in
chapter 2 for details.
TOTAL RECEIVED PORT A
TOTAL RECEIVED PORT B
is a counter for total messages received with an error (bad port code, frame length too short).
TOTAL ERRORS
is a counter for total messages received with an error on Port A (PRP frame, but port received through
MISMATCHES PORT A
and LAN ID in the frame do not match).
is a counter for total messages received with an error on Port B (PRP frame, but port received through
MISMATCHES PORT B
and LAN ID in the frame do not match).
6
6-12

STATUS
PRP
Total Rx Port A:
Total Rx Port B:
MESSAGE
Total Errors:
MESSAGE
Mismatches Port A:
MESSAGE
Mismatches Port B:
MESSAGE
is a counter for total messages received (either from DANPs or from SANs) on Port A.
is a counter for total messages received (either from DANPs or from SANs) on Port B.
N60 Network Stability and Synchrophasor Measurement System
6 ACTUAL VALUES
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled