Table B–10: MODBUS MEMORY MAP (Sheet 33 of 70)
ADDR
REGISTER NAME
7044
Phase Overvoltage 1 Reset Delay
7045
Phase Overvoltage 1 Block
7047
Phase Overvoltage 1 Target
7048
Phase Overvoltage 1 Events
7049
...Repeated for Phase Overvoltage 2
7052
...Repeated for Phase Overvoltage 3
Disconnect (Breaker) Switch (Read/Write setting) (24 Modules)
74A0
Disconnect Switch 1 Function
74A1
Disconnect Switch 1 Name
74A4
Disconnect Switch 1 Mode
74A5
Disconnect Switch 1 Open
74A7
Disconnect Switch 1 Block Open
74A9
Disconnect Switch 1 Close
74AB
Disconnect Switch 1 Block Close
74AD
Disconnect Switch 1 Phase A / Three-pole Closed
74AF
Disconnect Switch 1 Phase A / Three-pole Opened
74B1
Disconnect Switch 1 Phase B Closed
74B3
Disconnect Switch 1 Phase B Opened
74B5
Disconnect Switch 1 Phase C Closed
74B7
Disconnect Switch 1 Phase C Opened
74B9
Disconnect Switch 1 Operate Time
74BA
Disconnect Switch 1 Alarm Delay
74BC
Disconnect Switch 1 Events
74BD
Reserved (2 items)
74BF
...Repeated for module number 2
74DE
...Repeated for module number 3
74FD
...Repeated for module number 4
741C
...Repeated for module number 5
743B
...Repeated for module number 6
755A
...Repeated for module number 7
7579
...Repeated for module number 8
7598
...Repeated for module number 9
75B7
...Repeated for module number 10
75D6
...Repeated for module number 11
75F5
...Repeated for module number 12
7614
...Repeated for module number 13
7633
...Repeated for module number 14
7652
...Repeated for module number 15
7671
...Repeated for module number 16
7690
...Repeated for module number 17
76AF
...Repeated for module number 18
76CE
...Repeated for module number 19
76ED
...Repeated for module number 20
770C
...Repeated for module number 21
772B
...Repeated for module number 22
774A
...Repeated for module number 23
7769
...Repeated for module number 24
Thermal Overload Protection (Read/Write Settings) (2 Modules)
7788
Thermal Protection 1 Function
7789
Thermal Protection 1 Source
778A
Thermal Protection 1 Base Current
778B
Thermal Protection 1 K Factor
778C
Thermal Protection 1 Trip Time Constant
778D
Thermal Protection 1 Reset Time Constant
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 600
s
0 to 4294967295
---
0 to 2
---
0 to 1
---
0 to 1
---
---
---
0 to 1
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 65.535
s
0 to 65.535
s
0 to 1
---
---
---
0 to 1
---
0 to 5
---
0.2 to 3
pu
1 to 1.2
---
0 to 1000
min.
0 to 1000
min.
B.4 MEMORY MAPPING
STEP
FORMAT
DEFAULT
0.01
F001
100
1
F300
0
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
---
F206
"SW 1"
1
F157
0 (3-Pole)
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
0.001
F001
70
0.001
F003
0
1
F102
0 (Disabled)
---
---
---
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
0.01
F001
80
0.05
F001
110
1
F001
45
1
F001
45
B-41