Modbus User Map; Real Time Clock - GE N60 Instruction Manual

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
DESCRIPTION
Virtual Input 1
1
Virtual Input 2
2
...
Virtual Input 64
64
PATH: SETTINGS
PRODUCT SETUP
 MODBUS USER MAP
5
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
ADDRESS
value of "0" in subsequent register
by "1". An address value of "0" in the initial register means "none" and values of "0" display for all registers. Different
values can be entered as required in any of the register positions.
ADDRESS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 REAL TIME
 CLOCK
The relay contains a real time clock (RTC) to create timestamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz-
ing time delivered to the relay.
The
SYNCHRONIZING SOURCE
which of the available external time sources to use for time synchronization. A setting of None causes the RTC and the syn-
chrophasor clock to free-run. A setting of PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/SNTP, or PP/PTP/IRIG-B/SNTP causes
5-64
VALUE


MODBUS USER MAP

ADDRESS
VALUE:
ADDRESS
MESSAGE
VALUE:
ADDRESS
MESSAGE
VALUE:
ADDRESS 256:
MESSAGE
VALUE:
line (converted from hex to decimal format). The corresponding value displays in the
lines automatically returns values for the previous
ADDRESS


REAL TIME CLOCK

SYNCRONIZING SOURCE:
None
REAL TIME CLOCK
MESSAGE
EVENTS: Disabled
IRIG-B SIGNAL TYPE:
MESSAGE
None
 PRECISION TIME
MESSAGE
 PROTOCOL (1588)
 SNTP PROTOCOL
MESSAGE
 LOCAL TIME
MESSAGE
setting configures the priority sequence of the time synchronization source, to determine
N60 Network Stability and Synchrophasor Measurement System
Range: 0 to 65535 in steps of 1
1:
0
0
Range: 0 to 65535 in steps of 1
2:
0
0
Range: 0 to 65535 in steps of 1
3:
0
0
Range: 0 to 65535 in steps of 1
0
0
Range: None, PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/
SNTP, PP/PTP/IRIG-B/SNTP
Range:Enabled, Disabled
Range:None, DC Shift, Amplitude Modulated
See below
See below
See below
5 SETTINGS
5.2.5 MODBUS USER MAP
line. A
VALUE
lines incremented
ADDRESS
5.2.6 REAL TIME CLOCK