GE N60 Instruction Manual page 485

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 70)
ADDR
REGISTER NAME
5F7D
Setting Group Function
5F7E
Setting Group Events
Setting Groups (Read Only)
5F7F
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Open Pole Detect (Read/Write Grouped Setting)
6040
Open Pole Detect Function
6041
Open Pole Detect Block
6043
Open Pole Detect A Aux Co
6045
Open Pole Detect B Aux Co
6047
Open Pole Detect C Aux Co
6049
Open Pole Detect Current Source
604A
Open Pole Detect Current Pickup
604B
Open Pole Detect Voltage Source
604C
Open Pole Detect Voltage Input
604D
Open Pole Detect Pickup Delay
604E
Open Pole Detect Reset Delay
604F
Open Pole Detect Target
6050
Open Pole Detect Events
6051
Open Pole Detect Broken Co
Overfrequency (Read/Write Setting) (4 Modules)
6470
Overfrequency 1 Function
6471
Overfrequency 1 Block
6473
Overfrequency 1 Source
6474
Overfrequency 1 Pickup
6475
Overfrequency 1 Pickup Delay
6476
Overfrequency 1 Reset Delay
6477
Overfrequency 1 Target
6478
Overfrequency 1 Events
6479
Reserved (4 items)
647D
...Repeated for Overfrequency 2
648A
...Repeated for Overfrequency 3
6497
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
65C8
Power Swing Detect Outer Limit Angle
65C9
Power Swing Detect Middle Limit Angle
65CA
Power Swing Detect Inner Limit Angle
65CB
Power Swing Detect Delay 1 Pickup
65CC
Power Swing Detect Delay 1 Reset
65CD
Power Swing Detect Delay 2 Pickup
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 1
---
0 to 1
---
0 to 5
---
---
---
---
---
---
---
---
---
---
---
---
---
0 to 1
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 4294967295
---
0 to 5
---
0.05 to 20
pu
0 to 5
---
0 to 1
---
0 to 65.535
s
0 to 65.535
s
0 to 2
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 4294967295
---
0 to 5
---
20 to 65
Hz
0 to 65.535
s
0 to 65.535
s
0 to 2
---
0 to 1
---
0 to 1
---
0 to 1
---
0 to 5
---
0 to 1
---
0.05 to 30
pu
0.1 to 500
ohms
40 to 90
degrees
0.1 to 500
ohms
40 to 90
degrees
40 to 140
degrees
40 to 140
degrees
40 to 140
degrees
0 to 65.535
s
0 to 65.535
s
0 to 65.535
s
B.4 MEMORY MAPPING
STEP
FORMAT
DEFAULT
1
F102
0 (Disabled)
1
F102
0 (Disabled)
1
F001
0
---
F203
(none)
---
F203
(none)
---
F203
(none)
---
F203
(none)
---
F203
(none)
---
F203
(none)
1
F102
0 (Disabled)
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F167
0 (SRC 1)
0.01
F001
20
1
F167
0 (SRC 1)
1
F102
0 (Disabled)
0.001
F001
60
0.001
F001
100
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
1
F102
0 (Disabled)
1
F300
0
1
F167
0 (SRC 1)
0.01
F001
6050
0.001
F001
500
0.001
F001
500
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F001
0
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
1
F513
0 (Two Step)
0.001
F001
600
0.01
F001
5000
1
F001
75
0.01
F001
5000
1
F001
75
1
F001
120
1
F001
90
1
F001
60
0.001
F001
30
0.001
F001
50
0.001
F001
17
B-39
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents