5.4 SYSTEM SETUP
updated, and the 5 second timer is restarted. This setting enables or disables the control. When enabled, all 16 oper-
ands for each aggregator are active; when disabled all 16 operands for each aggregator remain reset.
Table 5–13: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
ELEMENT:
Synchrophasor, phasor data,
concentrator
as above
as above
as above
as above
as above
as above
5
as above
IEC 61850-90-5 AGGREGATOR 1 CONFIGURATION
PMU AGGREGATOR1: NAME: A user-defined visible string of characters (max. 56) to identify the source of the
stream. This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the
IEC 61850 MSVID filed in the output stream.
AGGREGATOR1: PHYSICAL PORT: This setting determines the physical ports through which the synchrophasor traf-
fic is transmitted. The range is 1, 2, 3.
PMU AGGREGATOR1: UDP: This setting selects the UDP port number that is used by this dataset for network report-
ing. A default setting value for IEC 6150-90-5 is provided.
PMU AGGREGATOR1: NUMBER OF ASDUs: This setting sets the number of Application Service Data Units
(ASDUs) from 1 through to 4.
Table 5–14: NUMBER OF ASDU
SETTINGS FOR ASDU
1
2
3
4
m) CONTROL BLOCKS

PATH: SETTINGS
SYSTEM SETUP
 IEC 90-5 MSVCB
 CONFIGURATION
5-134
OPERAND SYNTAX
AGTR1 PDC CNTRL 1
AGTR1 PDC CNTRL 2
AGTR1 PDC CNTRL 3
AGTR1 PDC CNTRL 16
AGTR2 PDC CNTRL 1
AGTR2 PDC CNTRL 2
AGTR2 PDC CNTRL 3
AGTR1 PDC CNTRL 16
TRANSMISSION
ASDU at T0 (current values)
ASDU at T-1 (previous values) + ASDU at T0 (current values)
ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) +
ASDU at T0 (current values)
PHASOR MEASUREMENT UNIT
MSVCB 1 SVENA:
OFF
MSVCB 1 CLIENT CTRL:
MESSAGE
OFF
MSVCB 1 SVENA DEFLT:
MESSAGE
OFF
MSVCB 1 CONFREV:
MESSAGE
1
N60 Network Stability and Synchrophasor Measurement System
OPERAND DESCRIPTION
Phasor data concentrator asserts control bit 1, as
received via the network.
Phasor data concentrator asserts control bit 2 as
received via the network.
Phasor data concentrator asserts control bit 3 as
received via the network.
Phasor data concentrator asserts control bit 16, as
received via the network.
Phasor data concentrator asserts control bit 1 as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network.
Phasor data concentrator asserts control bit 16, as
received via the network.

IEC 90 – 5 MSVCB01 (02-04) CONFIGURATION
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1 to 4294967295
5 SETTINGS
GE Multilin