Using The Fault Tables; Controller Fault Table - GE PACSystems RXi User Manual

Distributed io controller
Table of Contents

Advertisement

Chapter 14. Diagnostics

Using the Fault Tables

14.2
To display the fault tables in Logic Developer software,
1. Go online with the PACSystems.
2. Select the Project tab in the Navigator, right click the Target node and choose
The controller fault table and the I/O fault table display the following information:
Controller Time/Date The current date and time of the CPU.
Last Cleared
Status
Total Faults
Entries Overflowed

14.2.1 Controller Fault Table

The controller fault table displays CPU faults such as password violations, configuration
mismatches, parity errors, and communications errors.
The controller fault table provides the following information for each fault:
Location
Description
Date/Time
Details
264
Diagnostics. The Fault Table Viewer appears.
The date and time faults were last cleared from the fault table. This information
is maintained by the PACSystems controller.
Displays Updating while the programmer is reading the fault table.
Displays Online when update is complete.
The total number of faults since the table was last cleared.
The number of entries lost because the fault table has overflowed since it was
cleared. Each fault table can contain up to 64 faults.
Identifies the location of the fault by rack.slot (always 0.0 for the RXi Controller).
Corresponds to a fault group, which is identified in the fault Details.
The date and time the fault occurred based on the CPU clock.
To view detailed information, click the fault entry. Refer to Viewing Controller Fault
Details below for more information.