5 SETTINGS
The GGIO1 status configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
 GGIO1 STATUS
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
NUMBER OF STATUS POINTS IN GGIO1
instantiated in the GGIO1 logical node. Changes to the
the N60 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
GGIO2 CF SPSCO 1(64)
 GGIO2 CF SPCSO 1
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are "0"
(status only), "1" (direct control), and "2" (SBO with normal security). The GGIO2 control points are used to control the N60
virtual inputs.
The GGIO4 analog configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
 GGIO4 ANALOG
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
NUMBER OF ANALOG POINTS
changed, the N60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
The
SCAN PERIOD OF ANALOG POINTS
GE Multilin
N60 Network Stability and Synchrophasor Measurement System


COMMUNICATIONS
IEC 61850 PROTOCOL
NUMBER OF STATUS
POINTS IN GGIO1: 8
GGIO1 INDICATION
Off
GGIO1 INDICATION
Off
GGIO1 INDICATION
Off
GGIO1 INDICATION 128
Off
setting specifies the number of "Ind" (single point status indications) that are
NUMBER OF STATUS POINTS IN GGIO1


COMMUNICATIONS
IEC 61850 PROTOCOL
GGIO2 CF SPCSO 1
CTLMODEL: 1


COMMUNICATIONS
IEC 61850 PROTOCOL
NUMBER OF ANALOG
POINTS IN GGIO4:
SCAN PERIOD OF
ANALOG POINTS: 1000 ms
 GGIO4 ANALOG
 MEASURED VALUE
 GGIO4 ANALOG
 MEASURED VALUE
 GGIO4 ANALOG
 MEASURED VALUE
 GGIO4 ANALOG 32
 MEASURED VALUE
setting determines how many analog data points will exist in GGIO4. When this value is
setting specifies the IEC 61850 report scan period in milliseconds.

GGIO1 STATUS CONFIGURATION
Range: 8 to 128 in steps of 8
Range: FlexLogic operand
1
Range: FlexLogic operand
2
Range: FlexLogic operand
3
Range: FlexLogic operand
setting will not take effect until

GGIO2 CONTROL CONFIGURATION
Range: 0, 1, or 2

GGIO4 ANALOG CONFIGURATION
Range: 4 to 32 in steps of 4
8
Range: 100 to 5000 ms in steps of 10
1
2
3
5.2 PRODUCT SETUP
5
5-51