GE N60 Instruction Manual page 474

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 20 of 70)
ADDR
REGISTER NAME
3B7E
...Repeated for Field Shared Input 15
3B87
...Repeated for Field Shared Input 16
Field Unit Contact Outputs (Read/Write Setting) (8 Modules)
3B90
Field Contact Output 1 ID (6 items)
3BB4
Field Output 1 Operate (6 items)
B
3BC0
Field Output 1 Seal In (6 items)
3BCC
Field Output 1 Events (6 items)
3BD2
...Repeated for Field Contact Output 2
3C14
...Repeated for Field Contact Output 3
3C56
...Repeated for Field Contact Output 4
3C98
...Repeated for Field Contact Output 5
3CDA
...Repeated for Field Contact Output 6
3D1C
...Repeated for Field Contact Output 7
3D5E
...Repeated for Field Contact Output 8
Field Unit Latching Outputs (Read/Write Setting) (8 Modules)
3DC7
Field Latching Output 1 ID
3DCD
Field Latching Output 1 Open
3DCF
Field Latching Output 1 Close
3DD1
Field Latching Output 1 Events
3DD2
Field Latching Output 1 Reserved (2 items)
3DD4
...Repeated for Field Latching Output 2
3DE1
...Repeated for Field Latching Output 3
3DEE
...Repeated for Field Latching Output 4
3DFB
...Repeated for Field Latching Output 5
3E08
...Repeated for Field Latching Output 6
3E15
...Repeated for Field Latching Output 7
3E22
...Repeated for Field Latching Output 8
Field Unit Shared Outputs (Read/Write Setting) (16 Modules)
3E30
Field Shared Output 1 ID
3E36
Field Shared Output 1 Operate
3E38
Field Shared Output 1 Unit Dest 1
3E39
Field Shared Output 1 Channel Dest 1
3E3A
Field Shared Output 1 Unit Dest 2
3E3B
Field Shared Output 1 Channel Dest 2
3E3C
Field Shared Output 1 Events
3E3D
...Repeated for Field Shared Output 2
3E4A
...Repeated for Field Shared Output 3
3E57
...Repeated for Field Shared Output 4
3E64
...Repeated for Field Shared Output 5
3E71
...Repeated for Field Shared Output 6
3E7E
...Repeated for Field Shared Output 7
3E8B
...Repeated for Field Shared Output 8
3E98
...Repeated for Field Shared Output 9
3EA5
...Repeated for Field Shared Output 10
3EB2
...Repeated for Field Shared Output 11
3EBF
...Repeated for Field Shared Output 12
3ECC
...Repeated for Field Shared Output 13
3ED9
...Repeated for Field Shared Output 14
3EE6
...Repeated for Field Shared Output 15
3EF3
...Repeated for Field Shared Output 16
Field Unit RTDs (Read/Write Setting) (8 Modules)
3F00
Field Unit RTD 1Name
3F06
Field Unit RTD 1 Origin
B-28
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
---
---
0 to 4294967295
---
0 to 4294967295
---
0 to 1
---
0 to 1
---
0 to 4294967295
---
0 to 4294967295
---
0 to 1
---
0 to 1
---
0 to 65535
---
0 to 4294967295
---
0 to 8
---
1 to 15
---
0 to 8
---
1 to 15
---
0 to 1
---
0 to 1
---
0 to 24
---
APPENDIX B
STEP
FORMAT
DEFAULT
---
F205
"FCO U /OUT"
1
F300
0
1
F300
0
1
F102
1 (Enabled)
---
F205
"FLO Ux /LO"
1
F300
0
1
F300
0
1
F102
1 (Enabled)
1
F001
0
---
F205
"SO 1"
1
F300
0
1
F256
0 (none)
1
F001
1
1
F256
0 (none)
1
F001
1
1
F102
1 (Enabled)
1
F205
"RTD 1"
1
F253
0 (none)
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents