GE N60 Instruction Manual page 328

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.7 CONTROL ELEMENTS
FREQ RATE 1 MIN FREQUENCY: This setting defines minimum frequency level required for operation of the element.
The setting may be used to effectively block the feature based on frequency. For example, if the intent is to monitor an
increasing trend but only if the frequency is already above certain level, this setting should be set to the required fre-
quency level.
FREQ RATE 1 MAX FREQUENCY: This setting defines maximum frequency level required for operation of the ele-
ment. The setting may be used to effectively block the feature based on frequency. For example, if the intent is to mon-
itor a decreasing trend but only if the frequency is already below certain level (such as for load shedding), this setting
should be set to the required frequency level.
If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum
voltage supervision is 3 V.
NOTE
SETTINGS
FREQ RATE 1 FUNCTION:
Enabled = 1
FREQ RATE 1 BLOCK:
Off
5
SETTING
FREQ RATE 1 SOURCE:
Pos seq voltage (V_1)
Pos seq current (I_1)
Frequency (F)
5-210
SETTING
FREQ RATE 1 OV SUPV
PICKUP:
RUN
| V_1 | > PICKUP
SETTING
FREQ RATE 1 OC SUPV
PICKUP:
RUN
| I_1 | >PICKUP
SETTINGS
FREQ RATE 1 MIN
FREQUENCY:
FREQ RATE 1 MAX
FREQUENCY:
RUN
F > MIN & F < MAX
RUN
Calculate df/dt
Figure 5–87: FREQUENCY RATE OF CHANGE SCHEME LOGIC
N60 Network Stability and Synchrophasor Measurement System
SETTINGS
FREQ RATE 1 PICKUP
SETTINGS
DELAY:
FREQ RATE 1 TREND:
FREQ RATE 1 RESET
DELAY:
FREQ RATE 1 PICKUP:
t
RUN
PKP
df/dt > PICKUP
5 SETTINGS
FLEXLOGIC OPERANDS
FREQ RATE 1 OP
t
RST
FREQ RATE 1 DPO
FREQ RATE 1 PKP
832023A2.CDR
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents