5.5 FLEXLOGIC
Table 5–16: N60 FLEXLOGIC OPERANDS (Sheet 6 of 8)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
TELEPRO CH1 FAIL
Teleprotection
TELEPRO CH2 FAIL
channel tests
TELEPRO CH1 ID FAIL
TELEPRO CH2 ID FAIL
TELEPRO CH1 CRC FAIL
TELEPRO CH2 CRC FAIL
TELEPRO CH1 PKT LOST
TELEPRO CH2 PKT LOST
ELEMENT:
TELEPRO INPUT 1-1 On
Teleprotection
inputs/outputs
TELEPRO INPUT 1-16 On
TELEPRO INPUT 2-1 On
TELEPRO INPUT 2-16 On
ELEMENT:
THERMAL PROT 1 PKP
Thermal overload
THERMAL PROT 1 OP
protection
ELEMENT
TRIP BUS 1 PKP
Trip bus
TRIP BUS 1 OP
TRIP BUS 2...
5
ELEMENT:
UNDERFREQ 1 PKP
Underfrequency
UNDERFREQ 1 OP
UNDERFREQ 1 DPO
UNDERFREQ 2 to 6
FIXED OPERANDS
Off
On
INPUTS/OUTPUTS:
Cont Ip 1
Contact inputs
Cont Ip 2
Cont Ip 1
Cont Ip 2
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
current
(from detector on
form-A output only)
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
voltage
(from detector on
Cont Op 1
form-A output only)
Cont Op 2
INPUTS/OUTPUTS:
DIR ANA 1 DEADBAND
Direct analog inputs
DIR ANA 1 FORCE
DIR ANA 1 INTEGRITY
DIR ANA 2 to DIRECT ANA 32
INPUTS/OUTPUTS
DIRECT INPUT 1 On
Direct inputs
DIRECT INPUT 64 On
INPUTS/OUTPUTS:
RemDPS Ip 1 BAD
Remote double-
RemDPS Ip 1 INTERM
point status inputs
RemDPS Ip 1 OFF
RemDPS Ip 1 ON
REMDPS Ip 2...
INPUTS/OUTPUTS:
REMOTE INPUT 1 On
Remote inputs
REMOTE INPUT 2 On
REMOTE INPUT 3 On
REMOTE INPUT 32 On
5-144
OPERAND DESCRIPTION
Channel 1 failed
Channel 2 failed
The ID check for a peer relay on channel 1 has failed
The ID check for a peer relay on channel 2 has failed
CRC detected packet corruption on channel 1
CRC detected packet corruption on channel 2
CRC detected lost packet on channel 1
CRC detected lost packet on channel 2
Flag is set, Logic =1
Flag is set, Logic =1
Flag is set, Logic =1
Flag is set, Logic =1
Thermal overload protection 1 picked up
Thermal overload protection 1 operated
Asserted when the trip bus 1 element picks up.
Asserted when the trip bus 1 element operates.
Same set of operands as shown for TRIP BUS 1
Underfrequency 1 has picked up
Underfrequency 1 has operated
Underfrequency 1 has dropped out
Same set of operands as shown for UNDERFREQ 1 above
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
On
(will not appear unless ordered)
On
(will not appear unless ordered)
Off
(will not appear unless ordered)
Off
(will not appear unless ordered)
IOn
(will not appear unless ordered)
IOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOff
(will not appear unless ordered)
VOff
(will not appear unless ordered)
A deadband has triggered direct analog input 1
A user force operand has triggered direct analog input 1
An integrity timeout has triggered direct analog input 1
Same set of operands as per DIRECT ANA 1 above
Flag is set, logic=1
Flag is set, logic=1
Asserted while the remote double-point status input is in the bad state.
Asserted while the remote double-point status input is in the intermediate
state.
Asserted while the remote double-point status input is off.
Asserted while the remote double-point status input is on.
Same set of operands as per REMDPS 1 above
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
N60 Network Stability and Synchrophasor Measurement System