2 PRODUCT DESCRIPTION
2.3SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
NOTE
power system devices via communications or different output contacts. If not specified, the operate times given
here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
PHASE IOC
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0  CT rating: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0  CT rating
±1.5% of reading
Overreach:
<2%
Pickup delay:
0.00 to 600.00 s in steps of 0.01
Reset delay:
0.00 to 600.00 s in steps of 0.01
<16 ms at 3  pickup at 60 Hz
Operate time:
(Phase/Ground IOC)
<20 ms at 3  pickup at 60 Hz
(Neutral IOC)
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
SENSITIVE DIRECTIONAL POWER
Measured power:
3-phase, true RMS
Number of stages:
2
Characteristic angle:
0 to 359° in steps of 1
Calibration angle:
0.00 to 0.95° in steps of 0.05
Minimum power:
–1.200 to 1.200 pu in steps of 0.001
Pickup level accuracy:
±1% or ±0.001 pu, whichever is greater
Hysteresis:
2% or 0.001 pu, whichever is greater
Pickup delay:
0 to 600.00 s in steps of 0.01
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
<50 ms
PHASE UNDERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
102 to 103% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Curve shapes:
GE IAV Inverse;
Definite Time (0.1s base curve)
Curve multiplier:
Time dial = 0.00 to 600.00 in steps of
0.01
Curve timing accuracy
at <0.90 x pickup:
±3.5% of operate time or ±1/2 cycle
(whichever is greater) from pickup to
operate
GE Multilin
N60 Network Stability and Synchrophasor Measurement System

2.3.1 PROTECTION ELEMENTS

PHASE OVERVOLTAGE
Voltage:
Phasor only
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0.00 to 600.00 in steps of 0.01 s
30 ms at 1.10  pickup at 60 Hz
Operate time:
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
UNDERFREQUENCY
Minimum signal:
0.10 to 1.25 pu in steps of 0.01
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup + 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.
OVERFREQUENCY
Pickup level:
20.00 to 65.00 Hz in steps of 0.01
Dropout level:
pickup – 0.03 Hz
Level accuracy:
±0.001 Hz
Time delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
typically 4 cycles at 0.1 Hz/s change
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by
±0.5 cycles.

2.3 SPECIFICATIONS