5.4 SYSTEM SETUP
MSVCB 1 APPID: This setting allows the selection of a specific application ID for each sending device.
MSVCB 1 DEST IP Address: This is the destination multicast address IP address that is entered in Standard IPV4
address format. The valid range for IPv4 is from 224.0.0.0 to 239.255.255.255, but the UR does not test the address
entered.
MSVCB 1 Security: This setting selects the level of security and authentication used, as outlined in the following table,
and is in the form of an enumeration as per standard. The range is 0 to 2.
Shaded settings in the table are not supported in firmware 7.0.
ENUMERATION
NOTE
0
1
2
5
5-136
AUTHENTICATION
ENCRYPTION
no
no
yes
no
yes
yes